2022-02-10 13:21 作者:Acrel安科瑞张瑞豪  | 我要投稿

1安装使用指南

1 Installation and operation guide

1.1产品概述

1.1 Product overview

ASD500开关柜综合测控装置用3~35kV户内开关柜,适用于中置柜、手车柜、固定柜、环网柜等多种开关柜。具有一次回路模拟图及开关状态指示,高压带电显示及核相,自动温湿度控制,加热回路故障告警,分合闸回路完好指示、分合闸回路电压测量、预分预合闪光指示、电气节点无线测温,人体感应自动照明,语音提示,电参数测量RS485通讯接口等众多功能,集操作、显示于一体。

ASD series switch cabinet integrated measuring and control device is used for 3-35kV indoor switch cabinet, Applying to centrally installed switchgear, trolley cabinet, fixed switchgear, ring main unit and other various switch cabinets. With primary circuit mimetic diagram and switch status indicator, HV live displaying and nuclear phase, automatic temperature and humidity control, heating circuit fault alarm, wireless temperature measurement, tripping circuit and closing circuit supervising, tripping circuit and closing circuit control voltage measurement, pre-tripping circuit and pre-closing indicationbody induction auto lighting, voice prompt, electrical parameter measurement and RS485 communication interface and other numerous functions, it has integrated operation and display into one.

1.2型号说明

1.2 Description of types

1.1 ASD系列产品命名规则

Figure1.1 ASD Series Product naming rule

1.3产品型号及功能

1.3 Product model and function

1 ASD500产品型号及功能

Table1 ASD 500 Product specification and functions

型号Type

功能项

function

ASD500

产品图片

Product picture


开孔尺寸

Cut-out dimensions

220mm×165mm

一次模拟图

Primary circuit analog chart

标配

Standard

带电显示及自/核相

Live display and self-test/nuclear phase

标配

Standard

电磁闭锁出口

Electromagnetic lockout outle

一路

Configuration 1

温湿度控制

Temp./humidity control

1路传感,线4

Standard 1 sensor,line lengh 4meters

路加热,一路鼓风

Three heatingOne blowing

强制加热

Forced heating

标配

Standard

加热回路故障告警

Heating circuitFault alarm

标配

Standard

断电告警

Power off alarm

标配

Standard

语音提示

Voice prompts

标配

Standard

人体感应探头

Sensing probe for humanbody

标配

Standard

操作旋

Operating knob

可选

Optional

断路器分合次数显示

Beaker frequency shows

标配

Standard

预分预合闪光指示

pre-tripping circuit and pre-closing indication

可选

Optional

该功能仅限于配有带预分、预合功能的操作开关装置

This function only takes effect when there is a pre-tripping circuit and pre-closing indication switch

分闸、合闸完好指tripping circuit and closing circuit supervising,

标配

Standard

分合闸回路电压测量

tripping circuit and closing circuit control voltage measurement

标配

Standard

无线测温

Wireless temperature measurement

可选

Optional

主回路电力参数测量

Measure and display of power parameter

标配

Standard

RS485通讯接 Communication port

标配

Standard

1.4技术指标

1.4 Technical indexes

2 ASD500技术指标

Table2 ASD SeriesTechnical data

项目

Item

指标 Value

ASD500

额定输入

Rated input

接线方式

Wiring mode

3P3L3P4L

3P3L or3P4L

电压

Voltage

100V

电流

Current

5A

频率

frequency

50Hz

准确度

Accuracy rating

电流、电压

CurrentVoltage

0.5

0.5 class

有功功率无功功率

Active power

Reactive power

电能

Energy

分合闸回路电压

tripping circuit and closing circuit control voltage

1

1 class

环境温度

Environment temperature

±1

相对湿度

Relative humidity

±5%

装置工作电

Device Working power

AC 85~265VDC 100~300V

功耗

Power consumption

辅助电源

Auxiliary power

8VA

电压输入

Voltage input

0.5VA

电流输入

Current input

1VA

通讯

Communication

协议

protocol

MODBUS-RTUMODBUS-TCP

波特(bps)

Baud rate(bps)

24004800960019200

无线测温

Wireless temperature measurement

测温范Temperature measurement range

-50~+125

测温精度

Temperature measurement accuracy

±1

传感器电池寿命

Sensor battery life

5

5 year

传感器启动电流

starting current

5A

环境要求

Environmental

requirement

工作温度

Operating temperature

-10~55

相对湿度

Relative humidity

95%

平均无故障工作时间

Average work time without stoppage

50000

50000hour


1.5产品安装

1.5 Product installation

ASD500开关柜综合测控装置采用面板嵌入式安装,首先柜体盘面上制作规定尺寸的长方形槽孔,装置取下支架后嵌入槽孔,再用支架固定即可。

Panel embedded installation is adopted for ASD series switch cabinet integrated measuring and control device: firstly fabricate rectangular slot with stipulated size on cabinet face; embed the device into the slot after taking down the support and then fix by support.

1.5.1安装方法

1.5.1 Installation method


1.2 ASD500安装方法

Figure 1.2 Installation method of ASD500

1.5.2开孔尺寸(单位:毫米)

1.5.2 Hole size (unit: mm)

1.3 ASD500开孔尺寸

Figure 1.3Hole size diagram of ASD500

1.5.3温湿度传感器、无线温度收发器的安装

1.5.3 Installation of temperature and humidity sensor, wireless temperature transceiver

ASD500产品配套使用的温湿度传感器和无线测温接收器,可以采用导轨DIN35mm)安装方式,也可以使用螺栓固定方式,如1.4所示。

The temperature and humidity sensor and wireless temperature transceiver used as ancillary with ASD500 products can adopt guide rail (DIN35mm) installation or bolt fixing, as shown in Figure 1.4.



1.4 温湿度传感器和无线温度收发器安装方式

Figure 1.7 Installation methods of temperature and humidity sensor and wireless temperature transceiver

1.5.4无线温度传感器的安装

1.5.4 Installation of wireless temperature transceiver

无线温度传感器共有多种型号,分别对应螺栓固定、表带固定、扎带捆绑、合金片固定等安装方式。

There are several types of wireless temperature sensors and mounting methods correspondingly, i.e. bolted type, strap-secured type, tied type and alloy chip fixed type.

Parameter Type

wireless temperature sensors

ATE100M

ATE100

ATE200

ATE400

Power supply

Battery

CT inductive powered

Wireless frequency

470MHz

470MHz

Sampling frequency

25s

15s

Transmission

frequency

25s-5min

15s

Range of temperature

-50~+125

Accuracy

±1

Transmission

distance

150m in open area

Sevice life

>5 years(battery life)

>10 years

Installation

Magnetic

Bolted

Belt

Tied with cable tie

Application

between bus bar and cable joints

Bus bar, cable joints and fixed contact


1.5表带式无线温度传感ATE200

Figure 1.5Strap-secured wireless temperature sensor ATE200



1.6螺栓式无线温度传感ATE100 1.7磁吸无线温度传感ATE100M

Figure 1.6 Bolt wireless temperature sensorATE100Figure 1.7Magnetic wireless temperature sensorATE100M


1.8无源无线温度传感ATE400

Figure1.8Passive wireless temperature sensorATE400

迷你型无源无线温度传感器结构说明:

Mini type passive temperaturesensor structure introduction:

1温度传感器主体The core of wireless temperature sensor ATE400

2合金底座,与温度探头接alloy bottom, touched with temperature probe

3 锁扣,用于固定合金metal hasp, for fixing alloy chip

4——取电合金片,用于感应取alloy chip, for CT-powered

5 硅胶垫片用于支撑合金silicone gasket, used to support the alloy chip

6 合金片安装孔,用于安装合金片alloy chip hole, usedto install the alloy chip

1.9 ATE400结构说明

Figure1.9 structure introduction of ATE400

1.6接线方法

1.6 Wiring method

1.6.1接线端子

1.6.1 Wiring terminal


1.10 ASD500背面端子图

Figure 1.10 ASD500 back terminal diagram

1.6.2典型接线图

1.6.2 Typical wiring diagram


1.11 ASD开关量输入回路典型接线图

Figure 1.11 Typical wiring diagram of ASD switch input circuit


1.12 ASD开关量输出、高压带电显示回路及传感器典型接线图

Figure 1.19 Typical wiring diagram of ASD switch output, HV live displaying circuit and sensor


2界面简介

2.1 主界面说明

装置上电即显示主界面,点击屏幕上半部分,进湿的参数界面,如2.1-12.1-2所示,可通过点击导航栏,切换界面

2.1-1 2.1-2


2.1-3 2.1-4

2.2事件界面说明

点击导航栏内的事件菜单栏,可最多查50条告警记录,2.2-150条故障记录,如2.2-2



2.2-1 2.2-2

2.3参数界面说明

点击导航栏内的参数菜单栏,进入输密码界面,密码8,可在其子菜单栏内查湿分合的参数界面。









2.3-1 2.3-2 2.3-3









2.3-4 2.3-5 2.3-6

2.4调试界面说明

点击导航栏内的参数菜单栏,可在其子菜单栏内查I/O断路的参数界面;按子菜单栏的右翻键,输入密1008,进电量校节温校的参数界面。




2.4-1 2.4-2 2.4-3

3产品操作指南

3 Product operation guide

本操作说明主要针ASD500型开关柜综合测控装置

The operation instruction mainly aims at ASD300 switch cabinet integrated measuring and control device.

3.1显示介绍

3.1 Display introduction

3

4

5

1

6

6

7

2

3.1 ASD500前面板图

Figure 3.1 ASD500 front panel diagram

3 ASD500前面板功能说明

Table 3 Function description of ASD500 front panel

编号

No.

说明

Description

1

液晶显示屏

LCD

2

/就地操作开关

Remote/local operating switch

3

语音提示

Voice prompt

4

人体感应探测口

Human body induction detection port

5

储能旋钮

Stored energy knob

6

/合闸操作开关

Tripping/closing operating switch

7

高压带电显示及闭锁

HV live displaying and lock

3.2操作介绍

3.2 Operation introduction

3.2.1装置上电

3.2.1 Device power-on

接通符合要求的工作电源,装置即进入工作状态。

Connect the working power supply conforming to requirements and the device will enter working state.

3.2.2动态模拟图

3.2.2 Dynamic mimetic diagram

1断路器分、合闸指示

1) Breaker tripping/closing instructions

将断路器的分、合位置的辅助接点正确接入装置,装置上电正常工作后:

After the auxiliary contact of breaker tripping/closing position is correctly connected to device and the device is powered on for normal operation:

断路器处于合闸状态时,红色发光条3亮;

When the breaker is under close position, the red light bar 3 will be on;

断路器处于分闸状态时,绿色发光条4亮;

When the breaker is under open position, the green light bar 4 will be on;

2手车位置指示

2) Trolley position instructions:

将手车位置的辅助接点正确接入装置,装置上电正常工作后:

After the auxiliary contact of trolley position is correctly connected to device and the device is powered on for normal operation:

手车工作位置接点闭合时,红色发光条15(上下两)亮,指示小车位于工作位置;

When the operating position contact of trolley is closed, the red light bar 1bar5 (upper and lower ones) will be on and it indicates that the trolley is under operating position;

手车试验位置接点闭合时,绿色发光条26(上下两)亮,指示小车位于试验位置。

When the testing position contact of trolley is closed, the green light bar 2 bar 6 (upper and lower ones) will be on and it indicates that the trolley is under testing position.

3接地开关位置指示

3) Earthing switch position instructions

将接地开关的辅助接点正确接入装置,装置上电正常工作后:

After the auxiliary contact of trolley position is correctly connected to device and the device is powered on for normal operation:

输入接点闭合时,红色发光条9亮,表示接地开关处于合闸状态;

When the input contact is closed, the red light bar 9 will be on and it indicates that the earthing switch is under close position;

输入接点断开时,绿色发光条10亮,表示接地开关处于分闸状态。

When the input contact is disconnected, the green light bar 10 will be on and it indicates that the earthing switch is under open position.

4弹簧储能指示

4) Spring energy storage instructions

将储能机构的辅助接点正确接入装置,装置上电正常工作后,输入接点闭合,指示13亮,表示已储能。

After the auxiliary contact of energy storage mechanism is correctly connected in the device and the device is powered on for normal operation, the input contact will be closed and the indicator light 13 will be on and it indicates that energy has been stored.

注:开关量与指示灯对应关系可根据用户需求灵活设定!

Note: The correspondence of switch quantity and indicator light can be flexibly set according to user needs.

3.2.3高压带电显示及闭锁

3.2.3 HV live displaying and lock

装置的高压带电显示功能适用3.6-40.5kV/50Hz系统,与相应电压等级的传感器配合使用,显示主回路的带电情况。若传感器为用户自行配置,须保证其对地短路输出电流大于200μA

The HV live displaying function of device is Applicable to 3.6-40.5kV/50Hz system, which is used cooperatively with corresponding voltage classes to display the live condition of main circuit. If the sensor is allocated by the user itself, it must guarantee that the earthing short circuit output current shall be larger than 200μA.

在母线各相电压均小于额定电压15%时,强制闭锁处状态,前面板LOCK指示灯不亮接点闭合;母线任意相电压大于额定电压40%时,强制闭锁处状态LOCK指示灯亮接点断开。

When the voltage of all phases of busbar is less than 15% of rated voltage, the forced lock is underunlock status and theLOCK indicator light on front panel will not be on and theLock contact will be closed; when any phase voltage of busbar is larger than 40% of rated voltage, the forced lock is underlock status andLOCK indicator light will be on, thelock contact will be disconnected.

3.2.4报警继电器输出

3.2.4 Alarm relay output

自动定值越限告警继电器输出包括:过压、欠压、过流、温1超温、温2超温、无线温度传感器1高温、无线温度传感器2高温、无线温度传感器3高温、无线温度传感器4高温。

The auto definite value threshold crossing alert relay output includes: overvoltage, undervoltage, over current, temperature control 1 over temperature, temperature control 2 over temperature, wireless temperature sensor group 1 high temperature, wireless temperature sensor group 4 high temperature.

注意:需将相应的控制字选择才有效!

Note: It is valid only corresponding control word is selected asinput.

3.2.5自动温湿度控制

3.2.5 Auto temperature and humidity control

采用数字式温湿度控制,当环境相对湿85%,启动加热,当相对湿77%,停止加热;当环境温40,启动风扇鼓风,当温35,停止鼓风。当环境温5,启动加热,当环境温13,停止加热。ASD500可测量并采LCD显示现场环境的温度和湿度,带有加热、鼓风控制接点,可根据需要,自行设定加热、除湿、鼓风的上下限。传感器及其相关的参数及控制接点关系如2.2所示。

Digital temperature and humidity control.When the environment relative humidity is85%, start heating; when the relative humidity is77%, stop heating; when the environment temperature is40, start fan blast; when the temperature is35, stop blasting. When the environment temperature is5, start heating; when the environment temperature is13, stop heating.ASD500 can measure and adopt LCD to display the temperature and humidity of site environment. With heating, blast control contact, the upper and lower limit of heating, dehumidification and blast can be set according to requirements. The sensor and related parameters and the relationship between control contact are shown in Figure 2.2.


2.2 温湿度控制关系

Figure 2.2 Temperature and humidity control relationship

3.2.6无线测温

3.2.6 Wireless temperature measurement

ASD500可选无线测温功能,装置通过无线温度接收器和各无线温度传感器直接进行温度值的传输,并采用液晶显示各无线温度传感器所测温度。通过菜单可设置无线温度传感器组的高温告警值,当测得温度值超出设定值时,装置报警继电器输出触点闭合。

ASD500 optional wireless temperature measurement functions. The device can directly transmit temperature values through wireless temperature receiver and all wireless temperature sensors and adopt LCD to display the temperature measured by all wireless temperature sensors. Through menu, the high temperature alarm value of wireless temperature sensor can be set. When the measured temperature value exceeds the set value, the device alarm relay output contact will be closed.

ASD主体与无线温度传感器的配对及校准(出厂已完成此工作,请勿随意进行此操作):

Matching and calibration of ASD main body and wireless temperature sensor:(Factory set, Do not change it at will):

1)ASD主体液晶操作进>节温设下的节温设置菜单。

1) ASD main body LC operation enters the thermostat setting menu underdebugging --->thermostat .

2)输入对应无线温度传感ID进行绑定,如查看标签TA1的无线温度传感器ID,将ID输入到节1A,输入完全部要配对传感器,按刷新键保存设置。

2)Enter the ID of the wireless temperature sensor corresponding to the wireless temperature sensor, such as the ID of the wireless temperature sensor with the tag TA1, enter this ID into the section temperature 1A, enter all the sensors to be matched, and press the refresh button to save the setting

3) ASD主体液晶操作进>节温校下的节温校准菜单。

3) ASD main body LC operation enters the thermostat calibration menu underdebugging --->thermostat.

4)更改需校准的节温值为准确值,按刷新键进行校准。

4)Change the section temperature to be calibrated to the exact value, press the refresh key to calibrate.

警告!出厂时包装箱内无线温度传感器ASD主体已配对和校准!安装时不可以与其ASD主体或无线温度传感器混用,无线温度传感器按其标ABC分别对应安装ABC

Warning! When it is delivered, the wireless temperature sensor in the packing case has already been matched with ASD main body and calibrated. When it is installed, it cannot be mixed with any other ASD main body or wireless temperature sensor. The wireless temperature sensor shall be respectively installed to A, B and C-phase according to its label A, B and C.

ASD主体与无线温度传感器可按以下方法进行配套识别:

The ASD body and the wireless temperature sensor can be identified in the following ways



ATE200标签

ATE200 Tag


ASD ATE400标签

ASD Tag ATE400 Tag

例如左图为一ASD主体的标签,如果ASD配套的传感器ATE100/ATE100M/ATE200/ATE400,则传感器的标签ASD主体条码的最3位数值一样。

For example, the left image is a label of an ASD body; if the sensor associated with the ASD is the ATE100/ATE100M/ATE200/ATE400, theGroup No. of the tag of the sensor is the same as the last 3-bit value of the ASD body barcode.

3.2.7智能语音防误提示

3.2.7 Intelligent voice error-preventing prompt

智能语音防误提示共有三种方式可选择。

Three methods can be selected for intelligent voice error-preventing prompt.

方式一:断路器、接地开关处于合闸状态,若误将小车从试验位置推至工作位置,装置语音提请分断路器,请分接地开;断路器处于合闸状态,若误将小车从试验位置推至工作位置,装置语音提请分断路;接地开关处于合闸状态,若误将小车从试验位置推至工作位置,装置语音提请分接地开

Method I: When the breaker and earthing switch are under close position, if the trolley is pushed to operating position from testing position by mistake, the device voice will promptplease disconnect the breaker and earthing switch; when the breaker is under open position, if the trolley is pushed to operating position from testing position by mistake, the device voice will promptplease disconnect the breaker; when the earthing switch is under open position, if the trolley is pushed to operating position from testing position by mistake, the device will voice promptplease disconnect the earthing switch.

方式二:断路器、接地开关处于合闸状态,若误将小车从试验位/工作位置推开,装置语音提请分断路器,请分接地开;断路器处于合闸状态,若误将小车从试验位/工作位置推开,装置语音提请分断路;接地开关处于合闸状态,若误将小车从试验位/工作位置推开,装置语音提请分接地开

Method II: When the breaker and earthing switch are under close position, if the trolley is pushed away from testing position/operating position by mistake, the device will voice promptplease disconnect the breaker and earthing switch; when the breaker is under close position, if the trolley is pushed away from testing position/operating position by mistake, the device will voice promptplease disconnect the breaker; when the earthing switch is under close position, if the trolley is pushed away from testing position/operating position by mistake, the device will voice promptplease disconnect the earthing switch.

方式三:断路器处于合闸状态,若误将小车从试验位/工作位置推开,装置语音提请分断路

Method III: When the breaker is under close position, if the trolley is pushed away from testing position/operating position by mistake, the device will voice promptplease disconnect the breaker.

3.2.8柜内照明功能

3.2.8 Cabinet lighting function

在装置参数菜单栏的动作界面on,强制打开柜内照明可修改照明时间;按off,将关闭柜内照明。

Press the Up key under the default main interface of device to open the lighting in the cabinet; then press the Up key again to close the lighting in the cabinet.

3.2.9人体感应

3.2.9 Human body induction

LCD背光自动控制开启(背光延时设置不0),人离开装置一段时间后,自动关闭柜内照明和液晶背光;当有人接近装置时,装置通过感应到周围红外场的变化感知有人接近,自动打开柜内照明及液晶背光。

LCD backlight auto control open (backlight delay shall not be set as 0): after leaving the device for a while, it will automatically close the lighting and LC backlight in the cabinet; when someone Approaches the device, the device will perceive that someone is Approaching through the change of surrounding infra-red field and automatically open the lighting and LC backlight in the cabinet.

3.2.10电力参数测量

3.2.10 Electric power parameter measurement

ASD500型开关柜综合测控装置可以测量主回路的电流、电压、有功功率、功率因数、电能等电力参数,可在装菜单中查看无功功率、视在功率等可以通过通讯口读出。

ASD500 switch cabinet integrated measuring and control device can measure the current, voltage, active power, power factor, electric energy and other electric parameters of main circuit and check in theelectric quantity menu of device. the active power, Apparent power can be read out through communication port.

电参数的显示均为一次侧值,用户需选择正确的信号接入方式CTPT变比,以便正确显示测量值。

The display of electric parameter is all primary side value and the user shall select correct signal access way and CT, PT no-load voltage ratio to correctly display the measured value.

3.2.11带电显示自检

3.2.11 Self-inspection of live displaying

ASD500开关柜综合测控装置具有带电显示自检功能,可在装置面板的下方按键进行自检操作。按下按钮,对应指示灯亮并保持几秒钟,闭锁继电器端子断开(闭锁继电器端子不工作时处于常闭状态说明带电显示灯正常。

ASD500 switch cabinet integrated measuring and control device has live displaying self-inspection function, which can take self-inspection operation through the key under device panel. Press the button and corresponding LED will be lit for a few seconds and the lock relay will be open (it is normally closed when lock relay terminal is not working) and it indicates that the live displaying light is normal.

3.2.12核相功能

3.2.12 Nuclear phase function

ASD500开关柜综合测控装置具有带电显示核相功能,在装置接入高压信号经带电显示传感器后的信号后,可通过外接核相器接入装置的核相孔中,进行核相操作。该核相功能适用于市面上大多数的核相器(门槛电60V

ASD 500 switch cabinet integrated measuring and control device has live displaying nuclear phase function. After connecting the signal of live displaying sensor through HV signal, it can take nuclear phase operation by connecting the nuclear phase into the nuclear phase hole of device. This nuclear phase function is Applicable to great majority nuclear phase testers in the market (with threshold voltage60V).

注:本公司不配置核相器。

Note: Nuclear phase tester is not configured in our company.

1)上电后,装置自检,若自检通过,点击屏幕,进入电力参数显示界面,可查看电流、电压、功率、电能等各类电力参数(均为一次侧值)。

1) After power on, take self-inspection to the device. If the self-inspection passes, click on the screen,enter electric parameter display interface and check the current, voltage, power, electric energy and various kinds of electric parameters (all primary side values) through left key (or right key) switching.

2)湿菜单,即进入温湿度控制信息显示页面,该页面显示通12和通3所测得的环境温度和湿度。

2) Selecttemperature and humidity menu to enter the temperature and humidity control information display interface, as shown in the figure below. This page display the environment temperature and humidity measured through channel 1 channel 2 and channel 3 .

3)菜单可以设置装置工作的各类参数,包括电流电压信号的输入方式、变比,各类报警阈值、控制字,通讯参数等。该菜单下的内容需要用户口令才可以查看或修改,出厂设置口令0008

3) Parameter menu can set various kinds of operating parameters of device, including the input mode, no-load voltage ratio of current and voltage signal, various kinds of alarm threshold value, control word, communication parameters, etc. The content under the menu can be checked or modified only by user password. The factory set password is0008.

子菜单下可设置如电流电压接线方式,变比报警阀值等(电参数告警定值均采用二次侧值)。例如,过压投退设置,则当装置测得的电压值高于过压定值时,报警继电器输出触点闭合。

The current and voltage wiring mode and no-load voltage ratio alarm threshold value (electric parameter alarm definite values all adopt secondary side value) can be set underdefinite value submenu. For example, set the overvoltage in-service and out-of-service asin-service, when the measured voltage value of device is higher than the overvoltage definite value, the alarm rely output contact will be closed.

状态指子菜单下可设LED灯与开入的对应关系,也可设LED灯常亮ON)或者是常灭OFF)。

The correspondence of LED lamp and opening-in can be set understatus indicator submenu and LED lamp can be set as normally on (ON) or normally off (OFF).

子菜单下可设置设备的通讯地址及串口波特率。

The communication address and series rate can be set undercommunication submenu.

继电控子菜单下可设置开出模式,模式分为:

Opening-out mode can be set underrelay control submenu and the mode is classified into:

ON:设备上电后,继电器常闭触点为断开,常开触点为闭合(适用于手动控制)。

ON: After the device is powered on, the relay normally-closed contact will be disconnected and the normally-open contact will be closed (Applicable to manual control).

OFF:设备上电后,继电器常闭触点为闭合,常开触点为断开(适用于手动控制)。

OFF: After the device is powered on, the relay normally-closed contact will be closed and the normally-open contact will be disconnected (Applicable to manual control).

Def.:由内部逻辑控制继电器的闭合或断开。

Def: The interior logic will control the relay opening or closing.

子菜单下可进清电次数清恢复出操作,出厂设置口令1008

Clearing electric energy,Time reset andfactory reset operation can be taken underothers submenu and the factory setting password is1008.

注意:

Note:

1、恢复出厂后,除电参量校准数据,无线温度配对和校准数据外,其他所有参数都将恢复为出厂默认设置。恢复出厂后设备须重新上电后才生效!

1. After factory reset, except electric parameter calibration data, wireless temperature matching and calibration data, all the other parameters will be reset as factory default. After factory reset, the equipment must be powered on before it is effective.

2、电能清零后无法恢复,请谨慎使用此功能!

2. The electric energy will not be recovered after resetting, please be cautious to use this function!

液晶背子菜单下可设置液晶背光点亮时长。

LC backlight lightening length can be set underLC backlight submenu.

注意:对有人体感应的装置,该时间值也是人体感应控制照明输出的时间。

Note: For device with human body induction, the time value is also the time that human body induction controls lighting output.


2.4接线方式

Figure 2.4 Wiring mode

4通讯指南

4 Communication guide

在本章主要讲述如何利用软件通过通讯口来操控该系列仪表。本章内容的掌握需要您具MODBUS协议的知识储备并且通读了本册其他章节所有内容,对本产品功能和应用概念有较全面的了解。

In this chapter, it mainly introduces how to use software to control this series of instrument through communication port. To master this chapter, you must possess the knowledge reserve of MODBUS and have read all the contents in other chapters and have comprehensive understanding to the function and Application concept of the product.

本章内容包括:通讯应用格式详解,本机的应用细节及参量地址表。

The content of the chapter includes: detailed explanation of communication Application format, Application details and parameter address table.

4.1通讯格式详解

4.1 Detailed explanation of communication format

本节所举实例将尽可能的使用如下表所示的格式,数据为十六进制。

The format shown in table below will be used as much as possible for the examples in this section and the data is hexadecimal.

4.1.1读取数据(功能03H/04H

4.1.1 Reading data (function code 03H/04H)

此功能允许用户获得设备采集与记录的数据及系统参数。主机一次请求的数据个数没有限制,但不能超出定义的地址范围。

The function allows user to obtain the data and system parameters collected and recorded by equipment. There is no restriction to the data number primarily requested by main engine, but it shall not exceed the defined address scope.

例如,主机发送查询数据帧:

For example, main engine will send the query data frame:

地址

Addr

功能码

Fun

起始地址

Start Addr

寄存器数量

Register number

CRC16校验码

CRC 16 check code

High

Low

High

Low

High

Low

01H

03H

00H

30H

00H

03H

05H

C4H

装置返回响应数据帧:

The device will return the response data frame:

地址

Addr

功能码

Fun

字节数

byte

1

Date 1

2

Date 2

3

Date 3

CRC16校验码

CRC 16 check code

High

Low

High

Low

High

Low

High

Low

01H

03H

06H

00H

00H

00H

00H

00H

00H

21H

75H

3.1.2预置单个寄存器(功能06H

3.1.2 Preset single register (function code 06H)

此功能码允许用户改变单个寄存器的内容,可通过此功能码将工作参数写入装置。

The function code allows user to change the content of single register and operating parameters can be written into device through the function code.

例如,主机发送:

For example, the main engine sends:

地址

Addr

功能码

Fun

寄存器地址

Register address

预置值

Preset value

CRC16校验码

CRC 16 check code

High

Low

High

Low

High

Low

01H

06H

00H

03H

03H

E8H

74H

79H

装置返回响应数据帧:

The device returns to response data frame:

地址

Addr

功能码

Fun

寄存器地址

Register address

预置值

Preset value

CRC16校验码

CRC 16 check code

High

Low

High

Low

High

Low

01H

06H

00H

03H

03H

E8H

74H

79H

4.1.3预置多个寄存器(功能10H

4.1.3 Preset several registers (function code 10H)

此功能码允许用户改变多个寄存器的内容,可通过此功能码将工作参数写入装置。

The function code allows user to change the content of several registers and operating parameters can be written into device through the function code.

例如,主机发送:

For example, the main engine sends:

地址

Addr

功能码

Fun

起始地址

Start Addr

寄存器数

Register number

字节数

byte

预置1

Preset value 1

预置2

Preset value 1

CRC16

High

Low

High

Low

High

Low

High

Low

High

Low

01H

10H

00H

03H

00H

02H

04H

00H

28H

00H

64H

59H

32H

装置返回响应数据帧:

The device returns to response data frame:

地址

Addr

功能码

Fun

起始地址

Start Addr

寄存器数量

Register number

CRC16校验码

CRC 16 check code

高字节

High byte

低字节

Low byte

高字节

High byte

低字节

Low byte

高字节

High byte

低字节

Low byte

01H

10H

00H

03H

00H

02H

B1H

C8H

4.2参量地址表

4.2 Parameter address table

地址

Addr

参数

Parameter

属性

Read/Write

数值范围

Data range

数据类型

Data Type

0000H

通讯地址

Communication Addr

R/W

1-247

Word

0001H

通讯波特率

Communication Baud rate

R/W

24004800960019200

Word

0002H

电量输入方式

Electric parameter

Input mode

R/W

03P3L 1:3P4L

Word

0003H

电流变比

CT transformation

R/W

0.1~999.9x10

Word

0004H

电压变比

PT transformation ratio

R/W

0.1~999.9x10

Word

0005H

控制字

Control word

R/W

继电器报警控制字 0-off 1-on bit0: bit1: bit2: bit3-温湿1 bit4-温湿2 bit5:语音提 bit8~bit11节温1~4bit12:分合闸电压检测开启

Alarm relay control word:0-off1-on

bit0:Over voltagebit1:under voltagebit2:over loadbit3-Temp./humidity control 1 bit4-Temp./humidity control 2

bit5:Voice alert

bit8~bit11The section temperature group 1to4

bit12: tripping circuit and closing circuit control voltage measurement function enabled.

Word

0006H

通道A低温设定值

(加热I

Channel A Lo.temp.setting (heating I)

R/W

-45125

Word

0007H

通道A高温设定值

(鼓风)

Channel A Hi.temp.setting(air blowing)

R/W

0125

Word

0008H

通道A超温设定值(告警)

Channel A over-temp setting(alarm)

R/W

0125

Word

0009H

通道A高湿度设定值(加热I

Channel A Hi humidity setting(heating I)

R/W

1099%

Word

000AH

通道B低温设定值(加热II

Channel B Lo.temp. setting(heating II)

R/W

-45125

Word

000BH

通道B高温设定值

(鼓风)

Channel B Hi.temp.setting(air blowing)

R/W

0125

Word

000CH

通道B超温设定值(告警)

Channel B over-temp setting(alarm)

R/W

0125

Word

000DH

通道B高温设定值(加热II

Channel B Hi.temp.setting

(heating II)

R/W

1099%

Word

000EH

过压定值

Overvoltage setting

R/W

二次 1~999V

Secondary side 1~999V

Word

000FH

欠压定值

Undervoltage setting

R/W

二次 1~999V

Secondary side 1~999V

Word

0010H

过流定值

Overcurrent setting

R/W

二次 0~99.9Ax10

Secondary side 0~99.9Ax10

Word

0011H

液晶背光自动关闭时间

Liquid crystal back light Automatic closed time

R/W

0-999s0背光常亮

0-999s0Always bright backlight

Word

0012H

继电器输出

Relay output

R/W

bit0-4对应:

I、加II鼓风、告警、照明

Bit0-bit4

Heating I,heating II,air blowing,alarming,lighting

Word

0013H

开关量输入

Switching input

R

Bit0-bit7DI1-DI8

Bit0-bit7 corresponding DI1-DI8

Word

0014H

定值类报警状态

Value class alarm status

R

0-未告 1- bit0-bit3对应:通A低温、通A高温、通A超温、通A高湿

bit4-bit7对应:通B低温、通B高温、通B超温、通B高湿

bit8: bit9: bit10:bit11-bit12对应:第一路测温故障、第二路测温故

bit13-bit14对应:第一路加热器故第二路加热器故障

0-no alarm,1-alarmed.

Bit0-bit3 corresponding: Channel A Lo.temp,Channel A Hi.temp,Channel A over temp,Channel A Hi humidity

Bit4-bit7 corresponding: Channel B Lo.temp,Channel B Hi.temp,Channel B over temp,Channel B Hi humidity

Bit8:over voltage;Bit9:under voltage;

Bit10:over load

Bit11-bit12 corresponding: 1nd temperature sensor failure, 2nd temperature sensor failure

Bit13-bit14 corresponding: 1nd heating circuit

fault alarm, 2nd heating circuitfault alarm

Word

0015H

无线温度传感器高温报警状态

Wirless temperature sensor Hi.temp. alarm status

R

0:未报1:已报

bit0~bit11:1A~4C高温

0-no alarm,1-alarmed.

Bit0-bit 11 :

Section temperature 1A~ Section temperature 4C sensor Hi.temp.

Word

0016H

无线温度传感器低电压报警状态

Wirless temperature sensor low voltage alarm status

R

0:未报1:已报

bit0~bit11:1A~4C传感器低电压

0-no alarm,1-alarmed.

Bit0-bit 11 :

Section temperature 1A~ Section temperature 4C sensor low voltage.

Word

0017H

语音防误提示方式

Wrong voice prompts

R/W

1~2

Word

0018H

年份

Year

R/W

10~99(对2010~2099

10~99 corresponding: 2010~2099

Word

0019H

月份

Month

R/W

1~12

Word

001AH

高位:日

HighDay

R/W

1~31

Word

低位:时

LowHour

R/W

0~23

Word

001BH

高位:分

HighMinute

R/W

0~59

Word

低位:秒

LowSecond

R/W

0~59

Word

001CH

无线温度传感器1高温定

Wireless temperature sensor group 1 high temperature setting

R/W

0~125

Word

001DH

无线温度传感器2高温定

Wireless temperature sensor group 2 high temperature setting

R/W

0~125

Word

001EH

无线温度传感器3高温定

Wireless temperature sensor group 3 high temperature setting

R/W

0~125

Word

001FH

无线温度传感器4高温定

Wireless temperature sensor group 4 high temperature setting

R/W

0~125

Word

0020~0022H

1A 1B 1C温度值

1A 1B 1C temperature value

R

0~125.0(x10)

Word

0023~0025H

2A 2B 2C温度值

2A 2B 2C temperature value

R

0~125.0(x10)

Word

0026~0028H

3A 3B 3C温度值

3A 3B 3C temperature value

R

0~125.0(x10)

Word

0029~002BH

4A 4B 4C温度值

4A 4B 4C temperature value

R

0~125.0(x10)

Word

002CH

A温度值

Channel A

temperature value

R

-45.0125.0(x10)

Word

002DH

A湿度值

Channel A

humidity value

R

10.099.0%(x10)

Word

002EH

B温度值

Channel B

temperature value

R

-45.0125.0(x10)

Word

002FH

B湿度值

Channel B

humidity value

R

10.099.0%(x10)

Word

0030H

相电UA

Phase voltage UA

R

一次侧0~6553.5 kVx10)

Primary side: 0~6553.5 kVx10)

Word

0031H

相电UB

Phase voltage UB

R

一次侧0~6553.5 kVx10)

Primary side: 0~6553.5 kVx10)

Word

0032H

相电UC

Phase voltage UC

R

一次侧0~6553.5 kVx10)

Primary side:

Word

0033H

线电UAB

Line voltage UAB

R

一次侧0~6553.5 kVx10)

Primary side: 0~6553.5 kVx10)

Word

0034H

线电UBC

Line voltage UBC

R

一次侧0~6553.5 kVx10)

Primary side: 0~6553.5 kVx10)

Word

0035H

线电UAC

Line voltage UAC

R

一次侧0~6553.5 kVx10)

Primary side: 0~6553.5 kVx10)

Word

0036H

IA

R

一次侧0~6553.5 Ax10)

Primary side: 0~6553.5 kVx10)

Word

0037H

IB

R

一次侧0~6553.5 Ax10)

Primary side: 0~6553.5 kVx10)

Word

0038H

IC

R

一次侧0~6553.5 Ax10)

Primary side: 0~6553.5 kVx10)

Word

0039H

保留

Reserved

R

保留

Reserved

003AH-003BH

PA

R

一次侧0~6553.5kW

Primary side: 0~6553.5kW

float

003CH-003DH

PB

R

一次侧0~6553.5kW

Primary side: 0~6553.5kW

float

003EH-003FH

PC

R

一次侧0~6553.5kW

Primary side: 0~6553.5kW

float

0040H-0041H

Psum

R

一次侧0~6553.5kW

Primary side: 0~6553.5kW

float

0042H-0043H

QA

R

一次侧0~6553.5kvar

Primary side: 0~6553.5kvar

float

0044H-0045H

QB

R

一次侧0~6553.5kvar

Primary side: 0~6553.5kvar

float

0046H-0047H

QC

R

一次侧0~6553.5kvar

Primary side: 0~6553.5kvar

float

0048H-0049H

Qsum

R

一次侧0~6553.5kvar

Primary side: 0~6553.5kvar

float

004AH-004BH

PFA

R

0.0~1.0

float

004CH-004DH

PFB

R

0.0~1.0

float

004EH-004FH

PFC

R

0.0~1.0

float

0050H-0051H

Pfsum

R

0.0~1.0

float

0052H-0053H

SA

R

一次侧0~6553.5kVA

Primary side: 0~6553.5kVA

float

0054H-0055H

SB

R

一次侧0~6553.5kVA

Primary side: 0~6553.5kVA

float

0056H-0057H

SC

R

一次侧0~6553.5kVA

Primary side: 0~6553.5kVA

float

0058H-0059H

Ssum

R

一次侧0~6553.5kVA

Primary side: 0~6553.5kVA

float

005AH-005BH

Freq

R

45.0~65.0Hz

float

005CH-005DH

电能

Electrical energy

R

一次侧0.0~99999999.99kWh

Primary side: 0.0~99999999.99kWh

float

005EH

产品类型

Product Type

R/W

0~5对应100100G200300310320

Word

005FH

A低温报警返回值设定

Low temperature alarm return value of Channel A

R/W

-45125

Word

0060H

A高温报警返回High temperature alarm return value of Channel A

R/W

0125

Word

0061H

A超温报警返回值设定

Over temperature alarm return value of Channel A

R/W

0125

Word

0062H

A高湿报警返回值设定

High humidity alarm return value of Channel A

R/W

1099%

Word

0063H

B低温报警返回值设定

Low temperature alarm return value of Channel B

R/W

-45125

Word

0064H

B高温报警返回值设定

High temperature alarm return value of Channel B

R/W

0125

Word

0065H

B超温报警返回值设定

Over temperature alarm return value of Channel B

R/W

0125

Word

0066H

B高湿报警返回值设定

High humidity alarm return value of Channel B

R/W

1099%

Word

0067H

继电器告警延迟时间

Alarm delay

R/W

1.0-20.0 s*10

Word

0068H-0069H

——

R/W

——

006AH

强制加热时间

Manual heating time

R/W

0~120min 0:不加热

0~120min 0Manual heating not performed

6BH~199H

保留

Reserved

保留

Reserved

200H

工作语言:

Language:

R/W

0:中1:英文

0Chine 1English

Word

201H

1

Password 1

R/W

0-9999

Word

202H

2

Password 2

R/W

0-9999

Word

203H

轮询时间

Polling time

R/W

0~9999s 0:不轮询

0~9999s 0no poll

Word

204H

通讯数据位

Communication data bits

R/W

8~9

Word

205H

通讯停止位

Communication stop bit

R/W

0~201停止11.5停止22停止位

0~201 stop bit 11.5 stop bit 22 stop bit

Word

206H

通讯奇偶校验位

parity checkbit

R/W

0~20:无奇偶校1:奇校2:偶校验

0~20No parity 1Odd parity 2Even parity

Word

207H

无线通讯波特率

Wireless baud rate

R/W

24004800960019200

Word

208H

无线通讯数据位

Wireless communication data bit

R/W

8~9

Word

209H

无线通讯停止位

Wireless communication stop bit

R/W

0~201停止11.5停止22停止位

0~201 stop bit 11.5 stop bit 22 stop bit

Word

20AH

无线通讯奇偶校验位

Wireless communication parity check bit

R/W

0~20:无奇偶校1:奇校2:偶校验

0~20No parity 1Odd parity 2Even parity

Word

20BH

无线测温传感器1返回值

return value ofWireless temperature sensor group 1

R/W

0125

Word

20CH

无线测温传感器组2返回值

return value ofWireless temperature sensor group 2

R/W

0125

Word

20DH

无线测温传感器组3返回值

return value ofWireless temperature sensor group 3

R/W

0125

Word

20EH

无线测温传感器组4返回值

return value ofWireless temperature sensor group 4

R/W

0125

Word

20FH

DO1工作模式

DO1 output mode

R/W

0off 1on 2def.:normal

Word

210H

DO2工作模式

DO2output mode

R/W

0off 1on 2def.:normal

Word

211H

DO3工作模式

DO3output mode

R/W

0off 1on 2def.:normal

Word

212H

DO4工作模式

DO4output mode

R/W

0off 1on 2def.:normal

Word

213H

DO5工作模式

DO5output mode

R/W

0off 1on 2def:normal

Word

214H

DO6工作模式

DO6output mode

R/W

0off 1on 2def.:normal

Word

215H

LED灯配置

CB On LED configuration

R/W

0~24:1~25号灯

0~24 corresponding:1 ~ 25 lights

Word

216H

语音音量

Voice volume

R/W

0-7

Word

217H-21AH

保留

Reserved

R/W

保留

Reserved

Word

21BH

合闸电压

closing circuit control voltage

R

0-6553.5V*10

Word

21CH

分闸电压

tripping circuitcontrol voltage

R

0-6553.5V*10

Word

21DH

断路器分合次数

CB tripping and closing numbers

R

0~65535

Word

21EH

分合闸电压报警

Tripping/closing control voltage alarm

R

1:分闸过 2:合闸过

1: over voltage alarm of tripping control voltage 2: over voltage alarm of closing control voltage

Word

21FH

无线测温传感器类Wireless temperature sensor type

R

0ATE100 1:ATE300 0xff:未检测到传感器

0ATE100 1:ATE300 0xff:wireless sensor offline

Word

220H~22BH

外部无线测温传感器ID

ID of wireless temperature sensor

R

0~FFFF

ID号:检测到外部存在,但未绑定ID

0xFFFF:未检测到绑定ID

0~FFFF

With ID numberAn externally detected but unbound ID number

0xFFFFNo bound ID number detected

Word

22CH~237H

无线测温传感器状态

Wireless temperature sensor status

R

0~0xFFFF

ID号:已检测到节点对ID号存

0xFFFF:未检测到节点对ID号存在

0~0xFFFF

ID is detectedthe sensor of the detected ID is online

0xFFFFthe sensor is offline

Word

[1] R只读R/W可读,可写。

[2]×10×100×1000读取时实际值乘以相应的倍数上传,写入时应乘以相应的倍数写入

Note: [1] R-Read only; R/W-Readable, writable.

[2] ×10, ×100, ×1000-When reading, upload with practical value multiply corresponding times; when writing, write in by multiplying corresponding times.

5常见故障的诊断分析与排除方法

5Diagnostic analysis and troubleshooting of common faults

5.1辅助电源故障

5.1 Fault of auxiliary power supply

装置接通辅助电源后屏幕不亮?

The screen does not light after connecting the auxiliary power supply.

可能原因:外接端子线序错误。

Possible cause: the external terminal line sequence is wrong.

处理方法:拔温湿度I温湿度II无线测接口处的外接模块,重新上电装置判断

Handling method: pull out the external module at the joint oftemperature and humidity I,temperature and humidity II,wireless temperature measuring and re-power on to judge.

5.2环境温湿度显示故障

5.2 Fault of environment temperature and humidity display

温湿菜单下环境温湿度值无显示或显rupt

The environment and humidity value under temperature and humidity menu has no display or displaysrupt?

可能原因:温湿度控制字未投入或温湿度模块未接好。

Possible cause: The temperature and humidity control word is not input or temperature and humidity module is not well connected.

处理方法:

Handling method:

1)无显示时->菜单湿1退湿2退温湿3退设置为投入。

1)When there is no display:parameter -->definite value menu will set thetemperature and humidity 1 out-of-service ortemperature and humidity 2 out-of-serviceortemperature and humidity 3 out-of-service as in-service.

2)rupt时:检温湿度I温湿度II接口处的温湿度模块接入是否正确?

2) When displayingrupt: check whether the temperature and humidity module is correctly connected at the joint oftemperature and humidity I,temperature and humidity II.

5.3告警继电器动作故障

5.3 Fault of alarm relay operation

欠压,过压,过流,环境温度超温,无线节点温度高温定值越限而告警继电器不动作?

Undervoltage, overvoltage, environment temperature exceeds, wireless node high temperature definite value is out-of-limit and alarm relay does not work.

可能原因:相应的控制字未投入。

Possible cause: corresponding control word is not input.

处理方法->菜单将相应的控制字设置为投入。

Handling method:Parameter--> menu should set corresponding control word as input.

5.4一次模拟状态指示灯故障

5.4 Fault of primary simulated status indicator light

开关量输入与状态指示灯不对应或状态指示灯不亮?

Switch input and status indicator light is not corresponding or status indicator light is not on.

可能原因:状态指示灯设置错误。

Possible cause: status indicator light setting is wrong.

处理方法->状态指设置状态指示灯对应的开关量,如需常亮的设置ON,未使用的设置OFF

Handling method:Parameter--> status indicator should set corresponding switch quantity of status indicator light. For example, if it needs normally on, set it asON; if it is not used, set it asOFF.

5.5通信故障

5.5 Communication fault

上位机或后台软件与装置通信错误?

There is something wrong with communication between upper computer or background software with device.

可能原因:装置地址或串口参数设置错误。

Possible cause: Device address or serial port parameter setting is wrong.

处理方法->设置正确的装置地址或串口参数。

Handling method:Parameter--> communication should set correct device address or serial port parameters.

5.6节点温度值显示故障

5.6 Fault of node temperature value display

ASD菜单无温度值显示或无某一路温度值显示?

ASD main bodythermostat menu has no temperature value display or no temperature value display of some path.

可能原因:电池开关未打开或传感器不配对。

Possible cause: battery switch is not opened or sensor is mismatched.

处理方法:

Handling method:

1)查看无线温度传感器的电池开关是否拨ON端?(电池开关OFF端拨ON端后,无线温度传感器上的绿灯亮灭闪2次表示开关接通正常,否则重复拨动)。

1) Check whether the battery switch of wireless temperature sensor is dailed toON terminal (after battery switch is dialed to ON terminal from OFF terminal, the green light on wireless temperature sensor will flicker twice and it means that the switch is connected normally; otherwise, re-dial it0.

2)查ASD主体上的条码与无线温度传感器上的条码是否一致,不一致时找到对应的无线温度传感器更换或重新配对无线温度传感器(详见本说明2.2.6章节下ASD主体与无线温度传感器的配对及校部分)。

2) Check whether the code on ASD main body and wireless temperature sensor is consistent. When it is inconsistent, find out corresponding wireless temperature sensor to replace or rematch wireless temperature sensor (SeeMatching and calibration of ASD main body and wireless temperature sensor part under Section 2.2.6 of the specification).

A LW42凸轮开关安装说明

Annex A Installation instructions of LW42 cam switch



注:详细说明请到上海天逸电器股份有限公司官网:http://www.tayee.com.cn下载相应的文档查看。

Note: For detailed specification, please go to Shanghai Tayee Electrical Co., Ltd. official website: http://www.tayee.com.cn to download corresponding documents.

B储能开关安装说明

Annex B Installation specification of stored energy switch