ASD500开关柜综合测控装置
1安装使用指南
1 Installation and operation guide
1.1产品概述
1.1 Product overview
ASD500开关柜综合测控装置用于3~35kV户内开关柜,适用于中置柜、手车柜、固定柜、环网柜等多种开关柜。具有一次回路模拟图及开关状态指示,高压带电显示及核相,自动温湿度控制,加热回路故障告警,分合闸回路完好指示、分合闸回路电压测量、预分预合闪光指示、电气节点无线测温,人体感应自动照明,语音提示,电参数测量及RS485通讯接口等众多功能,集操作、显示于一体。
ASD series switch cabinet integrated measuring and control device is used for 3-35kV indoor switch cabinet, Applying to centrally installed switchgear, trolley cabinet, fixed switchgear, ring main unit and other various switch cabinets. With primary circuit mimetic diagram and switch status indicator, HV live displaying and nuclear phase, automatic temperature and humidity control, heating circuit fault alarm, wireless temperature measurement, tripping circuit and closing circuit supervising, tripping circuit and closing circuit control voltage measurement, pre-tripping circuit and pre-closing indication,body induction auto lighting, voice prompt, electrical parameter measurement and RS485 communication interface and other numerous functions, it has integrated operation and display into one.
1.2型号说明
1.2 Description of types
图1.1 ASD系列产品命名规则
Figure1.1 ASD Series Product naming rule
1.3产品型号及功能
1.3 Product model and function
表1 ASD500产品型号及功能
Table1 ASD 500 Product specification and functions
型号Type
功能项
function
ASD500
产品图片
Product picture
开孔尺寸
Cut-out dimensions
220mm×165mm
一次模拟图
Primary circuit analog chart
标配
Standard
带电显示及自检/核相
Live display and self-test/nuclear phase
标配
Standard
电磁闭锁出口
Electromagnetic lockout outle
一路
Configuration 1
温湿度控制
Temp./humidity control
标配1路传感器,线长4米
Standard 1 sensor,line lengh 4meters
三路加热,一路鼓风
Three heating,One blowing
强制加热
Forced heating
标配
Standard
加热回路故障告警
Heating circuitFault alarm
标配
Standard
断电告警
Power off alarm
标配
Standard
语音提示
Voice prompts
标配
Standard
人体感应探头
Sensing probe for humanbody
标配
Standard
操作旋钮
Operating knob
可选
Optional
断路器分合次数显示
Beaker frequency shows
标配
Standard
预分预合闪光指示
pre-tripping circuit and pre-closing indication
可选
Optional
(该功能仅限于配有带预分、预合功能的操作开关装置)
(This function only takes effect when there is a pre-tripping circuit and pre-closing indication switch)
分闸、合闸完好指示tripping circuit and closing circuit supervising,
标配
Standard
分合闸回路电压测量
tripping circuit and closing circuit control voltage measurement
标配
Standard
无线测温
Wireless temperature measurement
可选
Optional
主回路电力参数测量
Measure and display of power parameter
标配
Standard
RS485通讯接口 Communication port
标配
Standard
1.4技术指标
1.4 Technical indexes
表2 ASD500技术指标
Table2 ASD SeriesTechnical data
项目
Item
指标 Value
ASD500
额定输入
Rated input
接线方式
Wiring mode
3P3L或3P4L
3P3L or3P4L
电压
Voltage
100V
电流
Current
5A
频率
frequency
50Hz
准确度
Accuracy rating
电流、电压
Current、Voltage
0.5级
0.5 class
有功功率、无功功率
Active power、
Reactive power
电能
Energy
分合闸回路电压
tripping circuit and closing circuit control voltage
1级
1 class
环境温度
Environment temperature
±1℃
相对湿度
Relative humidity
±5%
装置工作电源
Device Working power
AC 85~265V,DC 100~300V
功耗
Power consumption
辅助电源
Auxiliary power
≤8VA
电压输入
Voltage input
≤0.5VA
电流输入
Current input
≤1VA
通讯
Communication
协议
protocol
MODBUS-RTU、MODBUS-TCP
波特率(bps)
Baud rate(bps)
2400、4800、9600、19200
无线测温
Wireless temperature measurement
测温范围Temperature measurement range
-50℃~+125℃
测温精度
Temperature measurement accuracy
±1℃
传感器电池寿命
Sensor battery life
≥5年
≥5 year
传感器启动电流
starting current
≥5A
环境要求
Environmental
requirement
工作温度
Operating temperature
-10℃~55℃
相对湿度
Relative humidity
≤95%
平均无故障工作时间
Average work time without stoppage
≥50000小时
≥50000hour

1.5产品安装
1.5 Product installation
ASD500开关柜综合测控装置采用面板嵌入式安装,首先柜体盘面上制作规定尺寸的长方形槽孔,装置取下支架后嵌入槽孔,再用支架固定即可。
Panel embedded installation is adopted for ASD series switch cabinet integrated measuring and control device: firstly fabricate rectangular slot with stipulated size on cabinet face; embed the device into the slot after taking down the support and then fix by support.
1.5.1安装方法
1.5.1 Installation method

图1.2 ASD500安装方法
Figure 1.2 Installation method of ASD500
1.5.2开孔尺寸(单位:毫米)
1.5.2 Hole size (unit: mm)
图1.3 ASD500开孔尺寸
Figure 1.3Hole size diagram of ASD500
1.5.3温湿度传感器、无线温度收发器的安装
1.5.3 Installation of temperature and humidity sensor, wireless temperature transceiver
与ASD500产品配套使用的温湿度传感器和无线测温接收器,可以采用导轨(DIN35mm)安装方式,也可以使用螺栓固定方式,如图1.4所示。
The temperature and humidity sensor and wireless temperature transceiver used as ancillary with ASD500 products can adopt guide rail (DIN35mm) installation or bolt fixing, as shown in Figure 1.4.


图1.4 温湿度传感器和无线温度收发器安装方式
Figure 1.7 Installation methods of temperature and humidity sensor and wireless temperature transceiver
1.5.4无线温度传感器的安装
1.5.4 Installation of wireless temperature transceiver
无线温度传感器共有多种型号,分别对应螺栓固定、表带固定、扎带捆绑、合金片固定等安装方式。
There are several types of wireless temperature sensors and mounting methods correspondingly, i.e. bolted type, strap-secured type, tied type and alloy chip fixed type.
Parameter Type
wireless temperature sensors
ATE100M
ATE100
ATE200
ATE400
Power supply
Battery
CT inductive powered
Wireless frequency
470MHz
470MHz
Sampling frequency
25s
15s
Transmission
frequency
25s-5min
15s
Range of temperature
-50℃~+125℃
Accuracy
±1℃
Transmission
distance
150m in open area
Sevice life
>5 years(battery life)
>10 years
Installation
Magnetic
Bolted
Belt
Tied with cable tie
Application
between bus bar and cable joints
Bus bar, cable joints and fixed contact

图1.5表带式无线温度传感器ATE200
Figure 1.5Strap-secured wireless temperature sensor ATE200


图1.6螺栓式无线温度传感器ATE100 图1.7磁吸式无线温度传感器ATE100M
Figure 1.6 Bolt wireless temperature sensorATE100Figure 1.7Magnetic wireless temperature sensorATE100M
图1.8无源无线温度传感器ATE400
Figure1.8Passive wireless temperature sensorATE400
迷你型无源无线温度传感器结构说明:
Mini type passive temperaturesensor structure introduction:
1——温度传感器主体The core of wireless temperature sensor ATE400
2——合金底座,与温度探头接触alloy bottom, touched with temperature probe
3 ——锁扣,用于固定合金片metal hasp, for fixing alloy chip
4——取电合金片,用于感应取电alloy chip, for CT-powered
5 ——硅胶垫片,用于支撑合金片silicone gasket, used to support the alloy chip
6 ——合金片安装孔,用于安装合金片alloy chip hole, usedto install the alloy chip
图1.9 ATE400结构说明
Figure1.9 structure introduction of ATE400
1.6接线方法
1.6 Wiring method
1.6.1接线端子
1.6.1 Wiring terminal

图1.10 ASD500背面端子图
Figure 1.10 ASD500 back terminal diagram
1.6.2典型接线图
1.6.2 Typical wiring diagram

图1.11 ASD开关量输入回路典型接线图
Figure 1.11 Typical wiring diagram of ASD switch input circuit

图1.12 ASD开关量输出、高压带电显示回路及传感器典型接线图
Figure 1.19 Typical wiring diagram of ASD switch output, HV live displaying circuit and sensor
2界面简介
2.1 主界面说明
装置上电即显示主界面,点击屏幕上半部分,进入“电量”、“温湿”、“节温”的参数界面,如图2.1-1~2.1-2所示,可通过点击导航栏,切换界面。
图2.1-1 图2.1-2

图2.1-3 图2.1-4
2.2事件界面说明
点击导航栏内的事件菜单栏,可最多查询50条告警记录,图2.2-1和50条故障记录,如图2.2-2。
图2.2-1 图2.2-2
2.3参数界面说明
点击导航栏内的参数菜单栏,进入输密码界面,密码为“8”,可在其子菜单栏内查看“通讯”、“时间”、“电力”、“温湿”、“节温”、“变送”、“继电”、“语音”、“状态”、“动作”、“分合闸”、“清除”的参数界面。
图2.3-1 图2.3-2 图2.3-3
图2.3-4 图2.3-5 图2.3-6
2.4调试界面说明
点击导航栏内的参数菜单栏,可在其子菜单栏内查看“I/O”、“断路器”、“信息”的参数界面;按子菜单栏的右翻键,输入密码“1008”,进入“电量校准”、“设置”、“节温校准”的参数界面。
图2.4-1 图2.4-2 图2.4-3
3产品操作指南
3 Product operation guide
本操作说明主要针对ASD500型开关柜综合测控装置。
The operation instruction mainly aims at ASD300 switch cabinet integrated measuring and control device.
3.1显示介绍
3.1 Display introduction
3
4
5
1
6
6
7
2
图3.1 ASD500前面板图
Figure 3.1 ASD500 front panel diagram
表3 ASD500前面板功能说明
Table 3 Function description of ASD500 front panel
编号
No.
说明
Description
1
液晶显示屏
LCD
2
远方/就地操作开关
Remote/local operating switch
3
语音提示
Voice prompt
4
人体感应探测口
Human body induction detection port
5
储能旋钮
Stored energy knob
6
分闸/合闸操作开关
Tripping/closing operating switch
7
高压带电显示及闭锁
HV live displaying and lock
3.2操作介绍
3.2 Operation introduction
3.2.1装置上电
3.2.1 Device power-on
接通符合要求的工作电源,装置即进入工作状态。
Connect the working power supply conforming to requirements and the device will enter working state.
3.2.2动态模拟图
3.2.2 Dynamic mimetic diagram
1)断路器分、合闸指示
1) Breaker tripping/closing instructions
将断路器的分、合位置的辅助接点正确接入装置,装置上电正常工作后:
After the auxiliary contact of breaker tripping/closing position is correctly connected to device and the device is powered on for normal operation:
断路器处于合闸状态时,红色发光条3亮;
When the breaker is under close position, the red light bar 3 will be on;
断路器处于分闸状态时,绿色发光条4亮;
When the breaker is under open position, the green light bar 4 will be on;
2)手车位置指示
2) Trolley position instructions:
将手车位置的辅助接点正确接入装置,装置上电正常工作后:
After the auxiliary contact of trolley position is correctly connected to device and the device is powered on for normal operation:
手车工作位置接点闭合时,红色发光条1、5(上下两条)亮,指示小车位于工作位置;
When the operating position contact of trolley is closed, the red light bar 1、bar5 (upper and lower ones) will be on and it indicates that the trolley is under operating position;
手车试验位置接点闭合时,绿色发光条2、6(上下两条)亮,指示小车位于试验位置。
When the testing position contact of trolley is closed, the green light bar 2、 bar 6 (upper and lower ones) will be on and it indicates that the trolley is under testing position.
3)接地开关位置指示
3) Earthing switch position instructions
将接地开关的辅助接点正确接入装置,装置上电正常工作后:
After the auxiliary contact of trolley position is correctly connected to device and the device is powered on for normal operation:
输入接点闭合时,红色发光条9亮,表示接地开关处于合闸状态;
When the input contact is closed, the red light bar 9 will be on and it indicates that the earthing switch is under close position;
输入接点断开时,绿色发光条10亮,表示接地开关处于分闸状态。
When the input contact is disconnected, the green light bar 10 will be on and it indicates that the earthing switch is under open position.
4)弹簧储能指示
4) Spring energy storage instructions
将储能机构的辅助接点正确接入装置,装置上电正常工作后,输入接点闭合,指示灯13亮,表示已储能。
After the auxiliary contact of energy storage mechanism is correctly connected in the device and the device is powered on for normal operation, the input contact will be closed and the indicator light 13 will be on and it indicates that energy has been stored.
注:开关量与指示灯对应关系可根据用户需求灵活设定!
Note: The correspondence of switch quantity and indicator light can be flexibly set according to user needs.
3.2.3高压带电显示及闭锁
3.2.3 HV live displaying and lock
装置的高压带电显示功能适用于3.6-40.5kV/50Hz系统,与相应电压等级的传感器配合使用,显示主回路的带电情况。若传感器为用户自行配置,须保证其对地短路输出电流大于200μA。
The HV live displaying function of device is Applicable to 3.6-40.5kV/50Hz system, which is used cooperatively with corresponding voltage classes to display the live condition of main circuit. If the sensor is allocated by the user itself, it must guarantee that the earthing short circuit output current shall be larger than 200μA.
在母线各相电压均小于额定电压的15%时,强制闭锁处于“解锁”状态,前面板上“LOCK”指示灯不亮,“闭锁”接点闭合;母线任意相电压大于额定电压的40%时,强制闭锁处于“闭锁”状态,“LOCK”指示灯亮,“闭锁”接点断开。
When the voltage of all phases of busbar is less than 15% of rated voltage, the forced lock is under“unlock” status and the“LOCK” indicator light on front panel will not be on and the“Lock” contact will be closed; when any phase voltage of busbar is larger than 40% of rated voltage, the forced lock is under“lock” status and“LOCK” indicator light will be on, the“lock” contact will be disconnected.
3.2.4报警继电器输出
3.2.4 Alarm relay output
自动定值越限告警继电器输出包括:过压、欠压、过流、温控1超温、温控2超温、无线温度传感器组1高温、无线温度传感器组2高温、无线温度传感器组3高温、无线温度传感器组4高温。
The auto definite value threshold crossing alert relay output includes: overvoltage, undervoltage, over current, temperature control 1 over temperature, temperature control 2 over temperature, wireless temperature sensor group 1 high temperature, wireless temperature sensor group 4 high temperature.
注意:需将相应的控制字选择为“投入”才有效!
Note: It is valid only corresponding control word is selected as“input”.
3.2.5自动温湿度控制
3.2.5 Auto temperature and humidity control
采用数字式温湿度控制,当环境相对湿度≥85%,启动加热,当相对湿度≤77%,停止加热;当环境温度≥40℃,启动风扇鼓风,当温度≤35℃,停止鼓风。当环境温度≤5℃,启动加热,当环境温度≥13℃,停止加热。ASD500可测量并采用LCD显示现场环境的温度和湿度,带有加热、鼓风控制接点,可根据需要,自行设定加热、除湿、鼓风的上下限。传感器及其相关的参数及控制接点关系如图2.2所示。
Digital temperature and humidity control.When the environment relative humidity is≥85%, start heating; when the relative humidity is≤77%, stop heating; when the environment temperature is≥40℃, start fan blast; when the temperature is≤35℃, stop blasting. When the environment temperature is≤5℃, start heating; when the environment temperature is≥13℃, stop heating.ASD500 can measure and adopt LCD to display the temperature and humidity of site environment. With heating, blast control contact, the upper and lower limit of heating, dehumidification and blast can be set according to requirements. The sensor and related parameters and the relationship between control contact are shown in Figure 2.2.

图2.2 温湿度控制关系
Figure 2.2 Temperature and humidity control relationship
3.2.6无线测温
3.2.6 Wireless temperature measurement
ASD500可选无线测温功能,装置通过无线温度接收器和各无线温度传感器直接进行温度值的传输,并采用液晶显示各无线温度传感器所测温度。通过菜单可设置无线温度传感器组的高温告警值,当测得温度值超出设定值时,装置报警继电器输出触点闭合。
ASD500 optional wireless temperature measurement functions. The device can directly transmit temperature values through wireless temperature receiver and all wireless temperature sensors and adopt LCD to display the temperature measured by all wireless temperature sensors. Through menu, the high temperature alarm value of wireless temperature sensor can be set. When the measured temperature value exceeds the set value, the device alarm relay output contact will be closed.
ASD主体与无线温度传感器的配对及校准(出厂已完成此工作,请勿随意进行此操作):
Matching and calibration of ASD main body and wireless temperature sensor:(Factory set, Do not change it at will):
1)ASD主体液晶操作进入“调试—>节温设置”下的节温设置菜单。
1) ASD main body LC operation enters the thermostat setting menu under“debugging --->thermostat .
2)输入对应无线温度传感器ID进行绑定,如查看标签为TA1的无线温度传感器的ID,将此ID输入到节温1A,输入完全部要配对传感器,按刷新键保存设置。
2)Enter the ID of the wireless temperature sensor corresponding to the wireless temperature sensor, such as the ID of the wireless temperature sensor with the tag TA1, enter this ID into the section temperature 1A, enter all the sensors to be matched, and press the refresh button to save the setting
3) ASD主体液晶操作进入“调试—>节温校准”下的节温校准菜单。
3) ASD main body LC operation enters the thermostat calibration menu under“debugging --->thermostat.
4)更改需校准的节温值为准确值,按刷新键进行校准。
4)Change the section temperature to be calibrated to the exact value, press the refresh key to calibrate.
警告!出厂时包装箱内无线温度传感器与ASD主体已配对和校准!安装时不可以与其他ASD主体或无线温度传感器混用,无线温度传感器按其标签A、B、C分别对应安装到A、B、C相。
Warning! When it is delivered, the wireless temperature sensor in the packing case has already been matched with ASD main body and calibrated. When it is installed, it cannot be mixed with any other ASD main body or wireless temperature sensor. The wireless temperature sensor shall be respectively installed to A, B and C-phase according to its label A, B and C.
ASD主体与无线温度传感器可按以下方法进行配套识别:
The ASD body and the wireless temperature sensor can be identified in the following ways:


ATE200标签
ATE200 Tag
ASD标签 ATE400标签
ASD Tag ATE400 Tag
例如左图为一台ASD主体的标签,如果此ASD配套的传感器为ATE100/ATE100M/ATE200/ATE400,则传感器的标签的“组号”和ASD主体条码的最后3位数值一样。
For example, the left image is a label of an ASD body; if the sensor associated with the ASD is the ATE100/ATE100M/ATE200/ATE400, the“Group No.” of the tag of the sensor is the same as the last 3-bit value of the ASD body barcode.
3.2.7智能语音防误提示
3.2.7 Intelligent voice error-preventing prompt
智能语音防误提示共有三种方式可选择。
Three methods can be selected for intelligent voice error-preventing prompt.
方式一:断路器、接地开关处于合闸状态,若误将小车从试验位置推至工作位置,装置语音提示“请分断路器,请分接地开关”;断路器处于合闸状态,若误将小车从试验位置推至工作位置,装置语音提示“请分断路器”;接地开关处于合闸状态,若误将小车从试验位置推至工作位置,装置语音提示“请分接地开关”。
Method I: When the breaker and earthing switch are under close position, if the trolley is pushed to operating position from testing position by mistake, the device voice will prompt“please disconnect the breaker and earthing switch”; when the breaker is under open position, if the trolley is pushed to operating position from testing position by mistake, the device voice will prompt“please disconnect the breaker”; when the earthing switch is under open position, if the trolley is pushed to operating position from testing position by mistake, the device will voice prompt“please disconnect the earthing switch”.
方式二:断路器、接地开关处于合闸状态,若误将小车从试验位置/工作位置推开,装置语音提示“请分断路器,请分接地开关”;断路器处于合闸状态,若误将小车从试验位置/工作位置推开,装置语音提示“请分断路器”;接地开关处于合闸状态,若误将小车从试验位置/工作位置推开,装置语音提示“请分接地开关”。
Method II: When the breaker and earthing switch are under close position, if the trolley is pushed away from testing position/operating position by mistake, the device will voice prompt“please disconnect the breaker and earthing switch”; when the breaker is under close position, if the trolley is pushed away from testing position/operating position by mistake, the device will voice prompt“please disconnect the breaker”; when the earthing switch is under close position, if the trolley is pushed away from testing position/operating position by mistake, the device will voice prompt“please disconnect the earthing switch”.
方式三:断路器处于合闸状态,若误将小车从试验位置/工作位置推开,装置语音提示“请分断路器”。
Method III: When the breaker is under close position, if the trolley is pushed away from testing position/operating position by mistake, the device will voice prompt“please disconnect the breaker”.
3.2.8柜内照明功能
3.2.8 Cabinet lighting function
在装置参数菜单栏的动作界面,按至on,强制打开柜内照明,可修改照明时间;按至off,将关闭柜内照明。
Press the Up key under the default main interface of device to open the lighting in the cabinet; then press the Up key again to close the lighting in the cabinet.
3.2.9人体感应
3.2.9 Human body induction
LCD背光自动控制开启(背光延时设置不为0),人离开装置一段时间后,自动关闭柜内照明和液晶背光;当有人接近装置时,装置通过感应到周围红外场的变化感知有人接近,自动打开柜内照明及液晶背光。
LCD backlight auto control open (backlight delay shall not be set as 0): after leaving the device for a while, it will automatically close the lighting and LC backlight in the cabinet; when someone Approaches the device, the device will perceive that someone is Approaching through the change of surrounding infra-red field and automatically open the lighting and LC backlight in the cabinet.
3.2.10电力参数测量
3.2.10 Electric power parameter measurement
ASD500型开关柜综合测控装置可以测量主回路的电流、电压、有功功率、功率因数、电能等电力参数,可在装置“电量”菜单中查看。无功功率、视在功率等可以通过通讯口读出。
ASD500 switch cabinet integrated measuring and control device can measure the current, voltage, active power, power factor, electric energy and other electric parameters of main circuit and check in the“electric quantity” menu of device. the active power, Apparent power can be read out through communication port.
电参数的显示均为一次侧值,用户需选择正确的信号接入方式及CT、PT变比,以便正确显示测量值。
The display of electric parameter is all primary side value and the user shall select correct signal access way and CT, PT no-load voltage ratio to correctly display the measured value.
3.2.11带电显示自检
3.2.11 Self-inspection of live displaying
ASD500开关柜综合测控装置具有带电显示自检功能,可在装置面板的下方按键进行自检操作。按下按钮,对应指示灯亮并保持几秒钟,闭锁继电器端子断开(闭锁继电器端子不工作时处于常闭状态),说明带电显示灯正常。
ASD500 switch cabinet integrated measuring and control device has live displaying self-inspection function, which can take self-inspection operation through the key under device panel. Press the button and corresponding LED will be lit for a few seconds and the lock relay will be open (it is normally closed when lock relay terminal is not working) and it indicates that the live displaying light is normal.
3.2.12核相功能
3.2.12 Nuclear phase function
ASD500开关柜综合测控装置具有带电显示核相功能,在装置接入高压信号经带电显示传感器后的信号后,可通过外接核相器接入装置的核相孔中,进行核相操作。该核相功能适用于市面上大多数的核相器(门槛电压≥60V)。
ASD 500 switch cabinet integrated measuring and control device has live displaying nuclear phase function. After connecting the signal of live displaying sensor through HV signal, it can take nuclear phase operation by connecting the nuclear phase into the nuclear phase hole of device. This nuclear phase function is Applicable to great majority nuclear phase testers in the market (with threshold voltage≥60V).
注:本公司不配置核相器。
Note: Nuclear phase tester is not configured in our company.
1)上电后,装置自检,若自检通过,点击屏幕,进入电力参数显示界面,可查看电流、电压、功率、电能等各类电力参数(均为一次侧值)。
1) After power on, take self-inspection to the device. If the self-inspection passes, click on the screen,enter electric parameter display interface and check the current, voltage, power, electric energy and various kinds of electric parameters (all primary side values) through left key (or right key) switching.
2)选择“温湿”菜单,即进入温湿度控制信息显示页面,该页面显示通道1、通道2、和通道3所测得的环境温度和湿度。
2) Select“temperature and humidity” menu to enter the temperature and humidity control information display interface, as shown in the figure below. This page display the environment temperature and humidity measured through channel 1 、channel 2 and channel 3 .
3)“参数”菜单可以设置装置工作的各类参数,包括电流电压信号的输入方式、变比,各类报警阈值、控制字,通讯参数等。该菜单下的内容需要用户口令才可以查看或修改,出厂设置口令为“0008”。
3) “Parameter” menu can set various kinds of operating parameters of device, including the input mode, no-load voltage ratio of current and voltage signal, various kinds of alarm threshold value, control word, communication parameters, etc. The content under the menu can be checked or modified only by user password. The factory set password is“0008”.
“定值”子菜单下可设置如电流电压接线方式,变比报警阀值等(电参数告警定值均采用二次侧值)。例如,过压投退设置为“投入”,则当装置测得的电压值高于过压定值时,报警继电器输出触点闭合。
The current and voltage wiring mode and no-load voltage ratio alarm threshold value (electric parameter alarm definite values all adopt secondary side value) can be set under“definite value” submenu. For example, set the overvoltage in-service and out-of-service as“in-service”, when the measured voltage value of device is higher than the overvoltage definite value, the alarm rely output contact will be closed.
“状态指示”子菜单下可设置LED灯与开入的对应关系,也可设置LED灯常亮(ON)或者是常灭(OFF)。
The correspondence of LED lamp and opening-in can be set under“status indicator” submenu and LED lamp can be set as normally on (ON) or normally off (OFF).
“通信”子菜单下可设置设备的通讯地址及串口波特率。
The communication address and series rate can be set under“communication” submenu.
“继电控制”子菜单下可设置开出模式,模式分为:
Opening-out mode can be set under“relay control” submenu and the mode is classified into:
ON:设备上电后,继电器常闭触点为断开,常开触点为闭合(适用于手动控制)。
ON: After the device is powered on, the relay normally-closed contact will be disconnected and the normally-open contact will be closed (Applicable to manual control).
OFF:设备上电后,继电器常闭触点为闭合,常开触点为断开(适用于手动控制)。
OFF: After the device is powered on, the relay normally-closed contact will be closed and the normally-open contact will be disconnected (Applicable to manual control).
Def.:由内部逻辑控制继电器的闭合或断开。
Def: The interior logic will control the relay opening or closing.
“其它”子菜单下可进行“清电能”,“次数清零”和“恢复出厂”操作,出厂设置口令为“1008”。
“Clearing electric energy”,“Time reset” and“factory reset” operation can be taken under“others” submenu and the factory setting password is“1008”.
注意:
Note:
1、恢复出厂后,除电参量校准数据,无线温度配对和校准数据外,其他所有参数都将恢复为出厂默认设置。恢复出厂后设备须重新上电后才生效!
1. After factory reset, except electric parameter calibration data, wireless temperature matching and calibration data, all the other parameters will be reset as factory default. After factory reset, the equipment must be powered on before it is effective.
2、电能清零后无法恢复,请谨慎使用此功能!
2. The electric energy will not be recovered after resetting, please be cautious to use this function!
“液晶背光”子菜单下可设置液晶背光点亮时长。
LC backlight lightening length can be set under“LC backlight” submenu.
注意:对有人体感应的装置,该时间值也是人体感应控制照明输出的时间。
Note: For device with human body induction, the time value is also the time that human body induction controls lighting output.
图2.4接线方式
Figure 2.4 Wiring mode
4通讯指南
4 Communication guide
在本章主要讲述如何利用软件通过通讯口来操控该系列仪表。本章内容的掌握需要您具有MODBUS协议的知识储备并且通读了本册其他章节所有内容,对本产品功能和应用概念有较全面的了解。
In this chapter, it mainly introduces how to use software to control this series of instrument through communication port. To master this chapter, you must possess the knowledge reserve of MODBUS and have read all the contents in other chapters and have comprehensive understanding to the function and Application concept of the product.
本章内容包括:通讯应用格式详解,本机的应用细节及参量地址表。
The content of the chapter includes: detailed explanation of communication Application format, Application details and parameter address table.
4.1通讯格式详解
4.1 Detailed explanation of communication format
本节所举实例将尽可能的使用如下表所示的格式,数据为十六进制。
The format shown in table below will be used as much as possible for the examples in this section and the data is hexadecimal.
4.1.1读取数据(功能码03H/04H)
4.1.1 Reading data (function code 03H/04H)
此功能允许用户获得设备采集与记录的数据及系统参数。主机一次请求的数据个数没有限制,但不能超出定义的地址范围。
The function allows user to obtain the data and system parameters collected and recorded by equipment. There is no restriction to the data number primarily requested by main engine, but it shall not exceed the defined address scope.
例如,主机发送查询数据帧:
For example, main engine will send the query data frame:
地址
Addr
功能码
Fun
起始地址
Start Addr
寄存器数量
Register number
CRC16校验码
CRC 16 check code
高 High
低Low
高High
低Low
高High
低Low
01H
03H
00H
30H
00H
03H
05H
C4H
装置返回响应数据帧:
The device will return the response data frame:
地址
Addr
功能码
Fun
字节数
byte
数据1
Date 1
数据2
Date 2
数据3
Date 3
CRC16校验码
CRC 16 check code
高
High
低Low
高
High
低
Low
高
High
低
Low
高
High
低
Low
01H
03H
06H
00H
00H
00H
00H
00H
00H
21H
75H
3.1.2预置单个寄存器(功能码06H)
3.1.2 Preset single register (function code 06H)
此功能码允许用户改变单个寄存器的内容,可通过此功能码将工作参数写入装置。
The function code allows user to change the content of single register and operating parameters can be written into device through the function code.
例如,主机发送:
For example, the main engine sends:
地址
Addr
功能码
Fun
寄存器地址
Register address
预置值
Preset value
CRC16校验码
CRC 16 check code
高High
低 Low
高High
低Low
高High
低Low
01H
06H
00H
03H
03H
E8H
74H
79H
装置返回响应数据帧:
The device returns to response data frame:
地址
Addr
功能码
Fun
寄存器地址
Register address
预置值
Preset value
CRC16校验码
CRC 16 check code
高High
低 Low
高High
低Low
高High
低Low
01H
06H
00H
03H
03H
E8H
74H
79H
4.1.3预置多个寄存器(功能码10H)
4.1.3 Preset several registers (function code 10H)
此功能码允许用户改变多个寄存器的内容,可通过此功能码将工作参数写入装置。
The function code allows user to change the content of several registers and operating parameters can be written into device through the function code.
例如,主机发送:
For example, the main engine sends:
地址
Addr
功能码
Fun
起始地址
Start Addr
寄存器数
Register number
字节数
byte
预置值1
Preset value 1
预置值2
Preset value 1
CRC16
高High
低Low
高High
低Low
高High
低Low
高High
低Low
高High
低Low
01H
10H
00H
03H
00H
02H
04H
00H
28H
00H
64H
59H
32H
装置返回响应数据帧:
The device returns to response data frame:
地址
Addr
功能码
Fun
起始地址
Start Addr
寄存器数量
Register number
CRC16校验码
CRC 16 check code
高字节
High byte
低字节
Low byte
高字节
High byte
低字节
Low byte
高字节
High byte
低字节
Low byte
01H
10H
00H
03H
00H
02H
B1H
C8H
4.2参量地址表
4.2 Parameter address table
地址
Addr
参数
Parameter
属性
Read/Write
数值范围
Data range
数据类型
Data Type
0000H
通讯地址
Communication Addr
R/W
1-247
Word
0001H
通讯波特率
Communication Baud rate
R/W
2400、4800、9600、19200
Word
0002H
电量输入方式
Electric parameter
Input mode
R/W
0:3P3L 1:3P4L
Word
0003H
电流变比
CT transformation
R/W
0.1~999.9(x10)
Word
0004H
电压变比
PT transformation ratio
R/W
0.1~999.9(x10)
Word
0005H
控制字
Control word
R/W
继电器报警控制字: 0-off 1-on bit0:过压 bit1:欠压 bit2:过载 bit3-温湿控1 bit4-温湿控2 bit5:语音提示 bit8~bit11节温组1~4bit12:分合闸电压检测开启
Alarm relay control word:0-off,1-on
bit0:Over voltage;bit1:under voltage;bit2:over load;bit3-Temp./humidity control 1; bit4-Temp./humidity control 2;
bit5:Voice alert;
bit8~bit11:The section temperature group 1to4;
bit12: tripping circuit and closing circuit control voltage measurement function enabled.
Word
0006H
通道A低温设定值
(加热I)
Channel A Lo.temp.setting (heating I)
R/W
-45~125℃
Word
0007H
通道A高温设定值
(鼓风)
Channel A Hi.temp.setting(air blowing)
R/W
0~125℃
Word
0008H
通道A超温设定值(告警)
Channel A over-temp setting(alarm)
R/W
0~125℃
Word
0009H
通道A高湿度设定值(加热I)
Channel A Hi humidity setting(heating I)
R/W
10~99%
Word
000AH
通道B低温设定值(加热II)
Channel B Lo.temp. setting(heating II)
R/W
-45~125℃
Word
000BH
通道B高温设定值
(鼓风)
Channel B Hi.temp.setting(air blowing)
R/W
0~125℃
Word
000CH
通道B超温设定值(告警)
Channel B over-temp setting(alarm)
R/W
0~125℃
Word
000DH
通道B高温设定值(加热II)
Channel B Hi.temp.setting
(heating II)
R/W
10~99%
Word
000EH
过压定值
Overvoltage setting
R/W
二次侧 1~999V
Secondary side 1~999V
Word
000FH
欠压定值
Undervoltage setting
R/W
二次侧 1~999V
Secondary side 1~999V
Word
0010H
过流定值
Overcurrent setting
R/W
二次侧 0~99.9A(x10)
Secondary side 0~99.9A(x10)
Word
0011H
液晶背光自动关闭时间
Liquid crystal back light Automatic closed time
R/W
0-999s,0—背光常亮
0-999s,0:Always bright backlight
Word
0012H
继电器输出
Relay output
R/W
bit0-4对应:
加热I、加热II、鼓风、告警、照明
Bit0-bit4:
Heating I,heating II,air blowing,alarming,lighting
Word
0013H
开关量输入
Switching input
R
Bit0-bit7对应DI1-DI8
Bit0-bit7 corresponding DI1-DI8
Word
0014H
定值类报警状态
Value class alarm status
R
0-未告警 1-告警 bit0-bit3对应:通道A低温、通道A高温、通道A超温、通道A高湿
bit4-bit7对应:通道B低温、通道B高温、通道B超温、通道B高湿
bit8:过压 bit9:欠压 bit10:过载bit11-bit12对应:第一路测温故障、第二路测温故障
bit13-bit14对应:第一路加热器故障第二路加热器故障
0-no alarm,1-alarmed.
Bit0-bit3 corresponding: Channel A Lo.temp,Channel A Hi.temp,Channel A over temp,Channel A Hi humidity
Bit4-bit7 corresponding: Channel B Lo.temp,Channel B Hi.temp,Channel B over temp,Channel B Hi humidity
Bit8:over voltage;Bit9:under voltage;
Bit10:over load
Bit11-bit12 corresponding: 1nd temperature sensor failure, 2nd temperature sensor failure
Bit13-bit14 corresponding: 1nd heating circuit
fault alarm, 2nd heating circuitfault alarm
Word
0015H
无线温度传感器高温报警状态
Wirless temperature sensor Hi.temp. alarm status
R
0:未报警1:已报警
bit0~bit11:节点1A~4C高温
0-no alarm,1-alarmed.
Bit0-bit 11 :
Section temperature 1A~ Section temperature 4C sensor Hi.temp.
Word
0016H
无线温度传感器低电压报警状态
Wirless temperature sensor low voltage alarm status
R
0:未报警1:已报警
bit0~bit11:节点1A~4C传感器低电压
0-no alarm,1-alarmed.
Bit0-bit 11 :
Section temperature 1A~ Section temperature 4C sensor low voltage.
Word
0017H
语音防误提示方式
Wrong voice prompts
R/W
1~2
Word
0018H
年份
Year
R/W
10~99(对应2010~2099)
10~99 corresponding: 2010~2099
Word
0019H
月份
Month
R/W
1~12
Word
001AH
高位:日
High:Day
R/W
1~31
Word
低位:时
Low:Hour
R/W
0~23
Word
001BH
高位:分
High:Minute
R/W
0~59
Word
低位:秒
Low:Second
R/W
0~59
Word
001CH
无线温度传感器组1高温定值
Wireless temperature sensor group 1 high temperature setting
R/W
0~125℃
Word
001DH
无线温度传感器组2高温定值
Wireless temperature sensor group 2 high temperature setting
R/W
0~125℃
Word
001EH
无线温度传感器组3高温定值
Wireless temperature sensor group 3 high temperature setting
R/W
0~125℃
Word
001FH
无线温度传感器组4高温定值
Wireless temperature sensor group 4 high temperature setting
R/W
0~125℃
Word
0020~0022H
1A 1B 1C温度值
1A 1B 1C temperature value
R
0~125.0℃(x10)
Word
0023~0025H
2A 2B 2C温度值
2A 2B 2C temperature value
R
0~125.0℃(x10)
Word
0026~0028H
3A 3B 3C温度值
3A 3B 3C temperature value
R
0~125.0℃(x10)
Word
0029~002BH
4A 4B 4C温度值
4A 4B 4C temperature value
R
0~125.0℃(x10)
Word
002CH
通道A温度值
Channel A
temperature value
R
-45.0~125.0℃(x10)
Word
002DH
通道A湿度值
Channel A
humidity value
R
10.0~99.0%(x10)
Word
002EH
通道B温度值
Channel B
temperature value
R
-45.0~125.0℃(x10)
Word
002FH
通道B湿度值
Channel B
humidity value
R
10.0~99.0%(x10)
Word
0030H
相电压UA
Phase voltage UA
R
一次侧:0~6553.5 kV(x10)
Primary side: 0~6553.5 kV(x10)
Word
0031H
相电压UB
Phase voltage UB
R
一次侧:0~6553.5 kV(x10)
Primary side: 0~6553.5 kV(x10)
Word
0032H
相电压UC
Phase voltage UC
R
一次侧:0~6553.5 kV(x10)
Primary side:
Word
0033H
线电压UAB
Line voltage UAB
R
一次侧:0~6553.5 kV(x10)
Primary side: 0~6553.5 kV(x10)
Word
0034H
线电压UBC
Line voltage UBC
R
一次侧:0~6553.5 kV(x10)
Primary side: 0~6553.5 kV(x10)
Word
0035H
线电压UAC
Line voltage UAC
R
一次侧:0~6553.5 kV(x10)
Primary side: 0~6553.5 kV(x10)
Word
0036H
IA
R
一次侧:0~6553.5 A(x10)
Primary side: 0~6553.5 kV(x10)
Word
0037H
IB
R
一次侧:0~6553.5 A(x10)
Primary side: 0~6553.5 kV(x10)
Word
0038H
IC
R
一次侧:0~6553.5 A(x10)
Primary side: 0~6553.5 kV(x10)
Word
0039H
保留
Reserved
R
保留
Reserved
003AH-003BH
PA
R
一次侧:0~6553.5kW
Primary side: 0~6553.5kW
float
003CH-003DH
PB
R
一次侧:0~6553.5kW
Primary side: 0~6553.5kW
float
003EH-003FH
PC
R
一次侧:0~6553.5kW
Primary side: 0~6553.5kW
float
0040H-0041H
Psum
R
一次侧:0~6553.5kW
Primary side: 0~6553.5kW
float
0042H-0043H
QA
R
一次侧:0~6553.5kvar
Primary side: 0~6553.5kvar
float
0044H-0045H
QB
R
一次侧:0~6553.5kvar
Primary side: 0~6553.5kvar
float
0046H-0047H
QC
R
一次侧:0~6553.5kvar
Primary side: 0~6553.5kvar
float
0048H-0049H
Qsum
R
一次侧:0~6553.5kvar
Primary side: 0~6553.5kvar
float
004AH-004BH
PFA
R
0.0~1.0
float
004CH-004DH
PFB
R
0.0~1.0
float
004EH-004FH
PFC
R
0.0~1.0
float
0050H-0051H
Pfsum
R
0.0~1.0
float
0052H-0053H
SA
R
一次侧:0~6553.5kVA
Primary side: 0~6553.5kVA
float
0054H-0055H
SB
R
一次侧:0~6553.5kVA
Primary side: 0~6553.5kVA
float
0056H-0057H
SC
R
一次侧:0~6553.5kVA
Primary side: 0~6553.5kVA
float
0058H-0059H
Ssum
R
一次侧:0~6553.5kVA
Primary side: 0~6553.5kVA
float
005AH-005BH
Freq
R
45.0~65.0Hz
float
005CH-005DH
电能
Electrical energy
R
一次侧:0.0~99999999.99kWh
Primary side: 0.0~99999999.99kWh
float
005EH
产品类型
Product Type
R/W
0~5对应:100、100G、200、300、310、320
Word
005FH
通道A低温报警返回值设定
Low temperature alarm return value of Channel A
R/W
-45~125℃
Word
0060H
通道A高温报警返回High temperature alarm return value of Channel A
R/W
0~125℃
Word
0061H
通道A超温报警返回值设定
Over temperature alarm return value of Channel A
R/W
0~125℃
Word
0062H
通道A高湿报警返回值设定
High humidity alarm return value of Channel A
R/W
10~99%
Word
0063H
通道B低温报警返回值设定
Low temperature alarm return value of Channel B
R/W
-45~125℃
Word
0064H
通道B高温报警返回值设定
High temperature alarm return value of Channel B
R/W
0~125℃
Word
0065H
通道B超温报警返回值设定
Over temperature alarm return value of Channel B
R/W
0~125℃
Word
0066H
通道B高湿报警返回值设定
High humidity alarm return value of Channel B
R/W
10~99%
Word
0067H
继电器告警延迟时间
Alarm delay
R/W
1.0-20.0 s(*10)
Word
0068H-0069H
——
R/W
——
006AH
强制加热时间
Manual heating time
R/W
0~120min 0:不加热
0~120min 0:Manual heating not performed
6BH~199H
保留
Reserved
保留
Reserved
200H
工作语言:
Language:
R/W
0:中文1:英文
0:Chine 1:English
Word
201H
密码1
Password 1
R/W
0-9999
Word
202H
密码2
Password 2
R/W
0-9999
Word
203H
轮询时间
Polling time
R/W
0~9999s 0:不轮询
0~9999s 0:no poll
Word
204H
通讯数据位
Communication data bits
R/W
8~9
Word
205H
通讯停止位
Communication stop bit
R/W
0~2:0:1停止位1:1.5停止位2:2停止位
0~2:0:1 stop bit 1:1.5 stop bit 2:2 stop bit
Word
206H
通讯奇偶校验位
parity checkbit
R/W
0~2:0:无奇偶校验1:奇校验2:偶校验
0~2:0:No parity 1:Odd parity 2:Even parity
Word
207H
无线通讯波特率
Wireless baud rate
R/W
2400、4800、9600、19200
Word
208H
无线通讯数据位
Wireless communication data bit
R/W
8~9
Word
209H
无线通讯停止位
Wireless communication stop bit
R/W
0~2:0:1停止位1:1.5停止位2:2停止位
0~2:0:1 stop bit 1:1.5 stop bit 2:2 stop bit
Word
20AH
无线通讯奇偶校验位
Wireless communication parity check bit
R/W
0~2:0:无奇偶校验1:奇校验2:偶校验
0~2:0:No parity 1:Odd parity 2:Even parity
Word
20BH
无线测温传感器组1返回值
return value ofWireless temperature sensor group 1
R/W
0~125℃
Word
20CH
无线测温传感器组2返回值
return value ofWireless temperature sensor group 2
R/W
0~125℃
Word
20DH
无线测温传感器组3返回值
return value ofWireless temperature sensor group 3
R/W
0~125℃
Word
20EH
无线测温传感器组4返回值
return value ofWireless temperature sensor group 4
R/W
0~125℃
Word
20FH
DO1工作模式
DO1 output mode
R/W
0:off 1:on 2:def.:normal
Word
210H
DO2工作模式
DO2output mode
R/W
0:off 1:on 2:def.:normal
Word
211H
DO3工作模式
DO3output mode
R/W
0:off 1:on 2:def.:normal
Word
212H
DO4工作模式
DO4output mode
R/W
0:off 1:on 2:def.:normal
Word
213H
DO5工作模式
DO5output mode
R/W
0:off 1:on 2:def:normal
Word
214H
DO6工作模式
DO6output mode
R/W
0:off 1:on 2:def.:normal
Word
215H
合闸LED灯配置
CB On LED configuration
R/W
0~24:对应1~25号灯
0~24 corresponding:1 ~ 25 lights
Word
216H
语音音量
Voice volume
R/W
0-7
Word
217H-21AH
保留
Reserved
R/W
保留
Reserved
Word
21BH
合闸电压
closing circuit control voltage
R
0-6553.5V(*10)
Word
21CH
分闸电压
tripping circuitcontrol voltage
R
0-6553.5V(*10)
Word
21DH
断路器分合次数
CB tripping and closing numbers
R
0~65535
Word
21EH
分合闸电压报警
Tripping/closing control voltage alarm
R
1:分闸过压 2:合闸过压
1: over voltage alarm of tripping control voltage 2: over voltage alarm of closing control voltage
Word
21FH
无线测温传感器类型Wireless temperature sensor type
R
0:ATE100 1:ATE300 0xff:未检测到传感器
0:ATE100 1:ATE300 0xff:wireless sensor offline
Word
220H~22BH
外部无线测温传感器的ID号
ID of wireless temperature sensor
R
0~FFFF:
有ID号:检测到外部存在,但未绑定的ID号
0xFFFF:未检测到绑定的ID号
0~FFFF:
With ID number:An externally detected but unbound ID number
0xFFFF:No bound ID number detected
Word
22CH~237H
无线测温传感器状态
Wireless temperature sensor status
R
0~0xFFFF
有ID号:已检测到节点对应ID号存在
0xFFFF:未检测到节点对应ID号存在
0~0xFFFF
ID is detected:the sensor of the detected ID is online
0xFFFF:the sensor is offline
Word
注:[1] R—只读;R/W—可读,可写。
[2]×10,×100,×1000—读取时实际值乘以相应的倍数上传,写入时应乘以相应的倍数写入。
Note: [1] R-Read only; R/W-Readable, writable.
[2] ×10, ×100, ×1000-When reading, upload with practical value multiply corresponding times; when writing, write in by multiplying corresponding times.
5常见故障的诊断分析与排除方法
5Diagnostic analysis and troubleshooting of common faults
5.1辅助电源故障
5.1 Fault of auxiliary power supply
装置接通辅助电源后屏幕不亮?
The screen does not light after connecting the auxiliary power supply.
可能原因:外接端子线序错误。
Possible cause: the external terminal line sequence is wrong.
处理方法:拔出“温湿度I”,“温湿度II”,“无线测温”接口处的外接模块,重新上电装置判断。
Handling method: pull out the external module at the joint of“temperature and humidity I”,“temperature and humidity II”,“wireless temperature measuring” and re-power on to judge.
5.2环境温湿度显示故障
5.2 Fault of environment temperature and humidity display
温湿菜单下环境温湿度值无显示或显示“rupt”?
The environment and humidity value under temperature and humidity menu has no display or displays“rupt”?
可能原因:温湿度控制字未投入或温湿度模块未接好。
Possible cause: The temperature and humidity control word is not input or temperature and humidity module is not well connected.
处理方法:
Handling method:
1)无显示时:“参数->定值”菜单将“温湿1投退”或“温湿2投退”或“温湿3投退”设置为投入。
1)When there is no display:“parameter -->definite value” menu will set the“temperature and humidity 1 out-of-service” or“temperature and humidity 2 out-of-service”or“temperature and humidity 3 out-of-service” as in-service.
2)显示“rupt”时:检查“温湿度I”,“温湿度II”接口处的温湿度模块接入是否正确?
2) When displaying“rupt”: check whether the temperature and humidity module is correctly connected at the joint of“temperature and humidity I”,“temperature and humidity II”.
5.3告警继电器动作故障
5.3 Fault of alarm relay operation
欠压,过压,过流,环境温度超温,无线节点温度高温定值越限而告警继电器不动作?
Undervoltage, overvoltage, environment temperature exceeds, wireless node high temperature definite value is out-of-limit and alarm relay does not work.
可能原因:相应的控制字未投入。
Possible cause: corresponding control word is not input.
处理方法:“参数->定值”菜单将相应的控制字设置为投入。
Handling method:“Parameter-->” menu should set corresponding control word as input.
5.4一次模拟状态指示灯故障
5.4 Fault of primary simulated status indicator light
开关量输入与状态指示灯不对应或状态指示灯不亮?
Switch input and status indicator light is not corresponding or status indicator light is not on.
可能原因:状态指示灯设置错误。
Possible cause: status indicator light setting is wrong.
处理方法:“参数->状态指示”设置状态指示灯对应的开关量,如需常亮的设置为“ON”,未使用的设置为“OFF”。
Handling method:“Parameter--> status indicator” should set corresponding switch quantity of status indicator light. For example, if it needs normally on, set it as“ON”; if it is not used, set it as“OFF”.
5.5通信故障
5.5 Communication fault
上位机或后台软件与装置通信错误?
There is something wrong with communication between upper computer or background software with device.
可能原因:装置地址或串口参数设置错误。
Possible cause: Device address or serial port parameter setting is wrong.
处理方法:“参数->通信”设置正确的装置地址或串口参数。
Handling method:“Parameter--> communication” should set correct device address or serial port parameters.
5.6节点温度值显示故障
5.6 Fault of node temperature value display
ASD主体“节温”菜单无温度值显示或无某一路温度值显示?
ASD main body“thermostat” menu has no temperature value display or no temperature value display of some path.
可能原因:电池开关未打开或传感器不配对。
Possible cause: battery switch is not opened or sensor is mismatched.
处理方法:
Handling method:
1)查看无线温度传感器的电池开关是否拨到“ON”端?(电池开关从OFF端拨到ON端后,无线温度传感器上的绿灯亮灭闪烁2次表示开关接通正常,否则重复拨动)。
1) Check whether the battery switch of wireless temperature sensor is dailed to“ON” terminal (after battery switch is dialed to ON terminal from OFF terminal, the green light on wireless temperature sensor will flicker twice and it means that the switch is connected normally; otherwise, re-dial it0.
2)查看ASD主体上的条码与无线温度传感器上的条码是否一致,不一致时找到对应的无线温度传感器更换或重新配对无线温度传感器(详见本说明书2.2.6章节下的“ASD主体与无线温度传感器的配对及校准”部分)。
2) Check whether the code on ASD main body and wireless temperature sensor is consistent. When it is inconsistent, find out corresponding wireless temperature sensor to replace or rematch wireless temperature sensor (See“Matching and calibration of ASD main body and wireless temperature sensor” part under Section 2.2.6 of the specification).
附A LW42凸轮开关安装说明
Annex A Installation instructions of LW42 cam switch


注:详细说明请到上海天逸电器股份有限公司官网:http://www.tayee.com.cn下载相应的文档查看。
Note: For detailed specification, please go to Shanghai Tayee Electrical Co., Ltd. official website: http://www.tayee.com.cn to download corresponding documents.
附B储能开关安装说明
Annex B Installation specification of stored energy switch