ABB 07AC91 GJR5252300R0101在模拟侧可以检测到的最小差异

16个模拟通道可以在两种操作模式下配置DIL开关(位于滑块下方
模块外壳右侧的盖子(见下图):
操作模式“12位”:8个模拟输入(端子4至19)加8个模拟输出(端子27至42),
可配置为±10 V或0…20 mA,解决方案12位
操作模式“8位”:16个模拟通道可成对配置,作为输入或输出
0…10 V或0…20 mA,解决方案8位
操作模式“8位”:
有关配置,请参阅前二页。
控制系统中的分辨率:
两个模拟通道的转换模拟值为
打包成一个字,每个字有8位(低字节和高字节
字节)。
在模拟侧可以检测到的最小差异(例如,在0…10V范围内的40mV)导致
将PLC程序中的数值更改为1。
示例:
0…10对0D。。。。255天
00小时。。。飞行时间
0…20毫安0D。。。。255天
00小时。。。飞行时间
模拟信号与转换后的数值之间的关系如下图所示。
如表所示,该模块在CS31系统总线上占用8个模拟输入和8个模拟输出。
如果模块在操作模式下被确认为“8位”
仅用于输入或仅用于输出,仅8个模拟输入或
CS31系统总线上使用了8个模拟输出。在里面
在这种情况下,未占用的输入或输出地址可以是
其他模块使用。
如果8号地址DIL开关切换到ON,则所有
通道编号更改为08,即地址AW n,00
AW n、08等的更改。这适用于地址
两种操作中输入和输出的分配
模式。

The 16 analog channels can be configured in two operating modes with DIL switches (located under the slide
cover on the right side of the module housing (see following figure):
Operating mode "12 bits": 8 analog inputs (terminals 4 to 19) plus 8 analog outputs (term. 27 to 42),
configurable for ±10 V or 0...20 mA, solution 12 bits
Operating mode "8 bits": 16 analog channels configurable in pairs as inputs or outputs for
0...10 V or 0...20 mA, solution 8 bits
Operating mode "8 bits":
For configuration please see second preceding page.
Resolution in the control system:
The converted analog values of two analog channels are
packed into a word with 8 bit each (low byte and high
byte).
The smallest difference that can be detected on the analog side (e.g. 40 mV in the range of 0...10 V) results in a
change of the numeric value by 1 in the PLC program.
Examples:
0...10 V 0D....255D
00H...FFH
0...20 mA 0D....255D
00H...FFH
The relationship between analog signal and converted numerical value is shown in the following figure.
As shown in the table, the module occupies 8 analog inputs and 8 analog outputs on the CS31 system bus.
If the module is confiugured in operating mode "8 bits"
only for inputs or only for outputs, only 8 analog inputs or
8 analog outputs are used on the CS31 system bus. In
this case, not occupied input or output addresses can be
used by other modules.
If the address DIL switch No. 8 is switched to ON, all
channel numbers change by 08, i.e. address AW n,00
changes to AW n,08, etc. This applies for the address
assignments for inputs and outputs in both operation
modes.
07KT98
07KT94
07KT93
07KT92
07KR31
07KP93
07DC92
07DC91
07CT41/1SBP260022R1001
07AI91
07AC91D
07AC91